05: ECO voltage range settings
06: Bypass enable/disable when UPS is off
07: Bypass voltage range setting
Interface
Setting
Parameter 2 & 3
:
Press the UP or Down key to choose the
acceptable high and low voltage values for the ECO mode.
HLS
: High line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges b7V and +24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter 3
ranges 3V and +12V of the nominal voltage.
LLS
: Low line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC, the setting in parameter
3 ranges between-7V and -24V of the nominal voltage.
For 100/110/115/120/127 VAC, the setting in parameter
3 ranges from -3V to -12V of the nominal voltage.
Interface
Setting
Parameter 3
:
Use it to activate or cancel the Bypass mode.
ENA
: Bypass enabled
DIS
: Bypass disabled
Interface
Setting
Parameter 2 & 3
:
Press the UP or Down key to choose the
acceptable high and low voltage values for Bypass operation
HLS
: High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264
: High voltage setting from 230VAC to 264VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
120-132
: High voltage setting from 120VAC to 132VAC
as set in parameter 3.
LLS
: Low voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
170-220
: Low voltage setting from 170VAC to 220VAC
as set in parameter 3.
For 100/110/115/120/127 VAC:
85-115
: Low voltage setting from 85VAC to 115VAC
as set in parameter 3