INSTALLATION REQUIREMENTS
If the appliance is to be sited near a disused natural draught flue it is recommended that the old flue should be
partially sealed off to prevent draughts, however some ventilation will be required to prevent condensation.
The appliance is designed to be wall mounted. It is possible to install the appliance onto certain types of com-
bustible materials - see section entitled ‘Clearances to combustible materials’.
In the event that the fire is sited near a disused or unserviceable fireplace served by a natural draught flue, any
existing under grate draught device should be sealed off to prevent loss of heat or creation of draughts. The
passageway into the flue should be partially sealed to prevent excessive draughts, however some ventilation
will be required in the old flue to prevent condensation and dampness. Advice should be sought from your
local building control officer.
ROOM SIZING
All Models : The room size should be a minimum of 23m3 (e.g. 10’1” x 10’1” x 8’) to allow adequate circula-
tion of air and ensure the correct operation of the fire. This volume may include adjacent spaces but these
spaces must not be separated by a door. To calculate a room size in cubic metres (m3) divide the room vol-
ume in cubic feet (ft3) by 35.3.
SITE REQUIREMENTS
This appliance is designed to be wall-hung. Do not recess any part of the appliance into the wall.
This Appliance may be installed in any room in a home except bedrooms and bathrooms.
Installation in living rooms is common, however other rooms such as kitchens, dining rooms and hallways are
permitted, providing a suitable natural gas supply is available, and rooms sizing and ventilation requirements
are strictly adhered to (see section 4.1).
The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gentle
draughts experienced within the home. It is not recommended, however that the appliance be installed in areas
where it is likely to be exposed to persistent strong draughts, that may be generated by outside doors or win-
dows, air vents etc. It is recommended that the appliance should not be installed within one metre of any air
vent.
2
APPLIANCE DATA
L23 Models
P23 Models
Gas Group
G20 Natural Gas CAT I2H
G20 Natural Gas CAT I2H
Inlet Pressure
20 mbar (+/- 2.0mbar)
20 mbar (+/- 2.0mbar)
Max Energy Input
Gross
2.0 kW
Gross
2.0 kW
Net
1.8 kW
Net
1.8 kW
Max Gas Rate
0.20 m3/h
0.20 m3/h
Min Energy Input
Gross
1.3 kW
Gross
1.0 kW
Net
1.15 kW
Net
0.9 kW
Pilot Energy Input
Gross
166 W
Gross
166 W
Net
150 W
Net
150 W
Burner Pressure High
18.7 mbar. (+/-1.5 mbar). Hot
18.7 mbar. (+/-1.5 mbar). Hot
18.6 mbar. (+/-1.5 mbar). Cold
18.6 mbar. (+/-1.5 mbar). Cold
Low
7.4 mbar. (+/-0.75 mbar). Hot
4.1 mbar. (+/-0.75 mbar). Hot
7.3 mbar (+/-0.75 mbar). Cold
4.0 mbar (+/-0.75 mbar). Cold
Main burner flow restrictor
Stereo 1.03mm (1/4” BSP)
Stereo 1.03mm (1/4” BSP)
Oxypilot
SIT/Bray 9082
SIT/Bray 9082
Gas Inlet Connection
8mm inlet restrictor elbow
8mm inlet restrictor elbow
Ignition
Piezo spark
Piezo spark
Spark Gap
4.0 mm (± 1.0mm)
4.0 mm (± 1.0mm)
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.
2.0
3.0
3.1
4.0