background image

PILOT ASSEMBLY

Clean the pilot assembly with a soft brush and blow through.  Check the aeration holes are free of any dirt or
lint.  Clean thoroughly internally, the connection can be removed from the base of the pilot unit using two span-
ners to make cleaning easier.  Do not damage or try to dismantle the pilot injector.

The unit is factory set and the only check necessary is to ensure the spark gap is correct.  See specifications for
gas setting.

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT

. If the pilot will not stay

lit there is a problem with dirt, the gas supply, or the thermocouple needs replacement. Modifications are dan-
gerous and can have a serious unseen effect on safety and therefore MUST not be done. Replacements must be
original manufacturers parts. Re-assemble in the reverse of removal. Ensure setting pressures are as stated in
Section 2; Appliance Data.

CATALYST

It is recommended that the catalysts are inspected for signs of damage and dirt during routine servicing proce-
dures. The expected life of the catalysts is in excess of 11,000 hours (10 years of normal use). After this time the
catalysts should be replaced.

If there are any deposits of dirt or soot on the catalyst they should be cleaned with a soft brush and a vacuum
cleaner. If removed for cleaning ensure the seals are in good condition before replacing the catalyst. New seals
will usually be required. The performance of the catalysts may be checked using a combustion gas analyser as
follows. Any analyser used should conform to EN 50379-3.

Ignite the fire as per the operating instructions, and run at maximum setting for 15 minutes. Position gas sample
probe directly over the catalysts via the outlet grille, on top of the appliance. Record the carbon dioxide (CO2)
concentration and then the carbon monoxide (CO) concentration as displayed by the analyser - also noting the
units in which the values are expressed. 

Most analysers display carbon dioxide (CO2) concentrations in percentage (%) terms and carbon monoxide
concentration in parts per million (ppm) terms.

In order to calculate the combustion ratio for the appliance (CO/CO2) it is first necessary to express both gas
concentrations in terms of percentage. To convert from parts per million (ppm) to a percentage (%) divide the
ppm figure by 10,000. Examples : 35ppm = 0.0035%, 15ppm = 0.0015%, 5ppm = 0.0005%.

Now divide the concentration of carbon monoxide (CO) expressed in percent by the concentration of carbon
dioxide (CO2) to obtain the appliance combustion ratio.

The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0.0015.
If replacing, firstly, remove the decorative frame/glass facia as described in section 8.4. The catalysts are located
on the top of the internal firebox and can be removed be unscrewing the retaining nuts securing the clamping
plates. Remove the catalysts their seals and discard. Refit the new catalysts and seals in reverse order, ensure the
catalysts and the glass door have good seals. 

TESTING FOR FIREBOX LEAKAGE

Appliances that are several years old or have been extensively dismantled should be checked for soundness. It
is important that all the products of combustion pass through the catalytic converter at the top of the firebox
before leaving the appliance. 

The firebox is heated by lighting for a few minutes to provide a flow through the firebox. The burner is then
shut off and a smoke pellet or match introduced at the base of the fire underneath the burner tray. Large
quantities of smoke will emerge from the top of the appliance, but none should emerge from the joints or gas-
ket faces, especially around the door. 

It is important to note that the appliance can never be expected to be 100% smoke tight and small quantities
of smoke may be seen in corners of joints and gasket faces etc without affecting safety when the fire is in
operation.

9

10.3

10.2

CO (%)
CO2 (%) = ratio

10.4

Summary of Contents for L23 BLACK

Page 1: ...ser for safekeeping Revision A 03 08 Country s of destination GB IE L23 CHESHIRE P23 MONET TRIO P23 ENIGMA FLUELESS GAS FIRE Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330 Fax 012...

Page 2: ...L23 Cheshire P23 Monet trio P23 Enigma silver glass...

Page 3: ...fire This volume may include adjacent spaces but these spaces must not be separated by a door In order to convert from cubic feet ft3 to cubic metres m3 divide the room volume in ft3 by 35 3 This app...

Page 4: ...only in a sufficiently ventilated space A minimum of 100cm2 15 5 in2 purpose provided ventilation is required for this appliance an openable window or louvre is also required To reduce the possibility...

Page 5: ...is common however other rooms such as kitchens dining rooms and hallways are permitted providing a suitable natural gas supply is available and rooms sizing and ventilation requirements are strictly a...

Page 6: ...s etc be positioned on the wall above the appliance The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire surround No combustible shelves should b...

Page 7: ...met 1 Fitting template GAS SUPPLY ROUTES There are four possible entry points for the gas supply pipework to enter the appliance firebox These entry points are knock out type holes Non concealed gas c...

Page 8: ...p wall plugs taking care to leave the screws protruding approximately 5mm from the wall Now hang the appliance onto these screws through the two key hole shaped holes in the back panel of the applianc...

Page 9: ...If under any circumstances the piezo electric spark fails the pilot cannot be lit man ually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main burne...

Page 10: ...ve packaging The glass facia panel is supported by four M6 screws which protrude from the front of the outer casing Ensure each screw is unscrewed approxi mately one turn from the fully screwed in pos...

Page 11: ...detailed in section 8 4 13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instruct...

Page 12: ...ed by the analyser also noting the units in which the values are expressed Most analysers display carbon dioxide CO2 concentrations in percentage terms and carbon monoxide concentration in parts per m...

Page 13: ...tray realign HT lead Fire runs for a time and then cuts off Loose or faulty thermocouple rectify Blocked pilot clean out Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If th...

Page 14: ...dicator bracket Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper low temperature surrounds etc may discolour if fitted too close to the fi...

Page 15: ...dis colouration may occur over time The appliance must not be positioned vertically within 100 mm of a carpeted floor rugs or fabric materials of any kind This dimension is measured vertically to the...

Page 16: ...y device ODS If the appliance shuts down during use for no apparent reason then several reasons may be suspected If a door or window has been opened creating a draught then pilot disturbance could be...

Reviews: