background image

VENTILATION AND ROOM SIZE (continued)

The room size should be a minimum of 23m3 (e.g. 10’1” x 10’1” x 8’) to allow adequate circulation of air and
ensure the correct operation of the fire. This volume may include adjacent spaces but these spaces must not
be separated by a door. To calculate a room size in cubic metres (m3) divide the room volume in cubic feet
(ft3) by 35.3.  This appliance is intended as a secondary source of heat only and should not be used in a room
without some form of background heating present.

OPERATING INSTRUCTIONS

The pilot is visible behind the left hand side of the burner.
The control knob is located on the lower right hand side of the outer
case. It is of a spherical design and is marked as shown in the dia-
gram to the right.

Push in and turn the control knob to the SPARK position, and hold
there for a few seconds. Continue turning anti-clockwise through the
spark click to the PILOT light position, ensuring the pilot has lit. If not,
return the knob clockwise, and repeat.

When the pilot lights after the spark, keep the knob depressed for
approximately ten seconds. Now release the knob and the pilot
should stay alight. If the pilot is extinguished during use, wait three
minutes before repeating the ignition procedure. 

To achieve the HIGH setting, push the control knob in slightly and
continue turning anti-clockwise to the high position. The main burn-
er should light after a few seconds.  To decrease the setting to LOW,
turn the control knob clockwise to the low setting.

To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the pilot
position and release. To turn the fire OFF, keep the knob pressed in, return to the off position and release.

COMBUSTION MONITORING SYSTEM

This fire is fitted with a combustion monitoring safety device (ODS).  If the appliance shuts down during use for
no apparent reason then several reasons may be suspected.  If a door or window has been opened creating a
draught, then pilot disturbance could be the problem and removal of the draught should resolve this.  The appli-
ance can then be re-lit in accordance with the previous section.

If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF,
call in your installer to check the appliance and ventilation. Remedial work must be carried out as required.  DO
NOT allow the appliance to be used until the appliance and installation is passed as safe. If the pilot continues
to be extinguished, you must call your installer to check the operation of the complete appliance.

CLEANING

Before carrying out any of the following operations, ensure that the appliance is OFF and completely cold. 
INNER GLASS PANEL -  This can be cleaned with a suitable glass cleaner, or propriety ceramic hob cleaner.
Test on a small area first.
GLASS FACIA PANEL - This should only be cleaned using a suitable glass cleaner. Test on a small area first.
PAINTED AREAS - These can be cleaned using a dry cloth.

SERVICING

The appliance should be checked on an annual basis to ensure it is working safely. The frequency of service
will depend on usage, but MUST be carried out at least once annually.  Servicing must be carried out by a
competent person, such as a CORGI registered installer.  The Installation instructions carry full servicing details
for the use of the installer.

LIST OF SPARE PARTS

PART NO.

ITEM

PART NO.

ITEM

F960002

Glass door assembly

F730023

Pilot assembly

FT003155/1

Gas valve

TRAY055

Burner tray

F780081

Catalyst 

F940136

Seal kit for Catalyst

4.0

5.0

3.0

‘OFF’ position

‘SPARK’ position

‘LOW’ position

‘HIGH’ position

7.0

6.0

8.0

F860473

As our policy is one of continuous improvement and development , we hope therefore you will understand we must retain the right
to amend details and/or specifications without prior notice.

3

Summary of Contents for L23 BLACK

Page 1: ...ser for safekeeping Revision A 03 08 Country s of destination GB IE L23 CHESHIRE P23 MONET TRIO P23 ENIGMA FLUELESS GAS FIRE Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330 Fax 012...

Page 2: ...L23 Cheshire P23 Monet trio P23 Enigma silver glass...

Page 3: ...fire This volume may include adjacent spaces but these spaces must not be separated by a door In order to convert from cubic feet ft3 to cubic metres m3 divide the room volume in ft3 by 35 3 This app...

Page 4: ...only in a sufficiently ventilated space A minimum of 100cm2 15 5 in2 purpose provided ventilation is required for this appliance an openable window or louvre is also required To reduce the possibility...

Page 5: ...is common however other rooms such as kitchens dining rooms and hallways are permitted providing a suitable natural gas supply is available and rooms sizing and ventilation requirements are strictly a...

Page 6: ...s etc be positioned on the wall above the appliance The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire surround No combustible shelves should b...

Page 7: ...met 1 Fitting template GAS SUPPLY ROUTES There are four possible entry points for the gas supply pipework to enter the appliance firebox These entry points are knock out type holes Non concealed gas c...

Page 8: ...p wall plugs taking care to leave the screws protruding approximately 5mm from the wall Now hang the appliance onto these screws through the two key hole shaped holes in the back panel of the applianc...

Page 9: ...If under any circumstances the piezo electric spark fails the pilot cannot be lit man ually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main burne...

Page 10: ...ve packaging The glass facia panel is supported by four M6 screws which protrude from the front of the outer casing Ensure each screw is unscrewed approxi mately one turn from the fully screwed in pos...

Page 11: ...detailed in section 8 4 13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instruct...

Page 12: ...ed by the analyser also noting the units in which the values are expressed Most analysers display carbon dioxide CO2 concentrations in percentage terms and carbon monoxide concentration in parts per m...

Page 13: ...tray realign HT lead Fire runs for a time and then cuts off Loose or faulty thermocouple rectify Blocked pilot clean out Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If th...

Page 14: ...dicator bracket Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper low temperature surrounds etc may discolour if fitted too close to the fi...

Page 15: ...dis colouration may occur over time The appliance must not be positioned vertically within 100 mm of a carpeted floor rugs or fabric materials of any kind This dimension is measured vertically to the...

Page 16: ...y device ODS If the appliance shuts down during use for no apparent reason then several reasons may be suspected If a door or window has been opened creating a draught then pilot disturbance could be...

Reviews: