Operating Manual CMGZ433
37
Integral I0
Use:
This value determines the behaviour of the „I“ component of the
controller. It is active if the BCD inputs are set to „0“. If the value
stored here is 1.00 the I controller will produce an output signal
changement of 1V/s resp. 1mA/s at a control error of 100N.
This parameter can be changed while the controller is enabled. The
new value is taken for the control loop when quit parameter mode.
Range:
0.01
to
100.00
Default:
1.00
Increment:
0.01
Unit:
[s]
Derivative D0
Use:
This value determines the behaviour of the „D“ component of the
controller. It is active if the BCD inputs are set to „0“.
This parameter can be changed while the controller is enabled. The
new value is taken for the control loop when quit parameter mode.
Range:
0.001
to
10.000
Default:
0.010
Increment:
0.001
Unit:
[s]
Proportional P1...P3
Use:
Description and function see
Proportional P0
. Active if the BCD
inputs are set to 1 resp. 2 resp. 3.
Integral I1...I3
Use:
Description and function see
Integral I0
. Active if the BCD inputs are
set to 1 resp. 2 resp. 3.
Derivative D1...D3
Use:
Description and function see
Derivative D0
. Active if the BCD inputs
are set to 1 resp. 2 resp. 3.
Alarm limit error
Use:
The digital output „Alarm controller error“ and the LED „Alarm
controller error“ will be activated if the control error exceeds the
tolerance set in this parameter.
Range:
0.1
to
100.0
Default:
10.0
Increment:
0.1
Unit:
[%]