Operating Manual CMGZ433
35
Scale instrument
Use:
The analog output for the external instrument (0...10V) provides the
nominal voltage when reaching the nominal force value. Using a
setting of 1.00, the nominal voltage will be 10V. The nominal voltage
is decreased when decreasing the setting value; it is increased when
increasing the setting value.
Range:
0.01
to
10.00
Default:
1.00
Increment:
0.01
Unit:
[-]
Limit 1 min / max
Use:
The digital output „Limit value 1“ can be set as a min- or a max limit
switch. That means, that the digital output will be activated when passing
over resp. passing under the value set under parameter
Limit value 1
.
Range:
Min,
Max
Default:
Max
Limit value 1
Use:
The digital output „Limit value 1“ will be activated if the threshold
value stored in this parameter is passed over resp. under (according to
setting in parameter
Limit 1 min / max
).
Range:
-9999
to
9999
Default:
0
Increment:
1
Unit:
[N,kN]
Limit 2 min / max
Use:
The digital output „Limit value 2“ can be set as a min- or a max limit
switch. That means, that the digital output will be activated when passing
over resp. passing under the value set under parameter
Limit value 2
.
Range:
Min,
Max
Default:
Min
Limit value 2
Use:
The digital output „Limit value 2“ will be activated if the threshold
value stored in this parameter is passed over resp. under (according to
setting in parameter
Limit 2 min / max
).
Range:
-9999
to
9999
Default:
0
Increment:
1
Unit:
[N,kN]
Language
Use:
With this parameter, the language in the display can be chosen.
Range:
English, German, French, Italian