Program
Code
Function
Code Description
Prod 1
Prod 2
Prod 3
Prod 4
Issue/Rev. 0.3 (8/97)
59
393
Transmitter Type
Enter:
"0" Single Channel
"1" Dual Channel
__
__
__
__
394-399
Unassigned at Present
400
Product Temperature & Density Directory
401-439
Unassigned at Present
440
Protection of Program
Enter:
"0" for Weights and Measures Mode
Codes 480-489
"1" for Program Mode
__
__
__
__
441
API Table & Product
Enter:
"00" No API Table "12" API Table 24A
"01" API Table 5A "13" API Table 24B
"02" API Table 5B "14" API Table 24D
"03" API Table 5D "15" API Table 53A
"04" API Table 6A "16" API Table 53B
"05" API Table 6B "17" API Table 53D
"06" API Table 6C "18" API Table 54
"07" API Table 6D "19" API Table 54A
"08" API Table 23A "20" API Table 54B
"09" API Table 23B "21" API Table 54C
"10" API Table 23D "22" API Table 54D
"11" API Table 24
___
___
___
___
442
Reference Density
Enter:
Five digit density
with floating decimal.
(e.g., 0999.9 to 0.9999
Depending on selection in
code 441).
_______ _______ _______ _______
443
Low Temperature
Enter:
Four digits. The
Alarm
first digit indicates polarity.
First digit "0" = Positive
First digit "1" = Negative
The last three digits
indicate temperature in whole
degrees. (e.g., 0020 = + 020)
Temperature units are dependent
on entry made in code 441
An entry of -999 will disable
this
feature.
_____ _____ _____ _____