Operating instructions TSM-21
Status as of 12 / 2021
Page 14
4
Technical data
Mains connection
95 - 253 V~
Mains frequency
50 Hz / 60 Hz
Output current, load
3 A~ max.
Output voltage, load
230 V~
Protection class
IP 54
(except for mains switch)
Fuse, load
3.15 A T
Fuse, control electronics
400 mA T
Mains connection,
mechanical
STASEI 2
Connection, load
800 mm cable + Hirschmann socket GDM 3016
Level sensor [E]
+24 V- / max. 50 mA / PNP
Switching level HI : 6 - 24V-
Switching level LO: 0 - 4V-
Controller disable [E]
+24 V- / max. 50 mA / PNP
Switching level HI : 6 - 24V-
Switching level LO: 0 - 4V-
Filling level sensor [E]
+24 V- / max. 50 mA / PNP
Switching level HI : 6 - 24V-
Switching level LO: 0 - 4V-
Malfunction [O]
+24 V- / max. 100 mA
Lack of workpieces [A]
+24 V- / max. 50 mA
Housing
ABS
Housing dimensions
(h)120 x (b)122 x (t)55 mm
Operating temperature
5...45° C
Relative humidity Max.95
%,
non-condensing
5 Error list
Danger:
Life-threatening danger due to electric current! Have repairs to the
230 V power network performed only by a qualified professional.
Problem/error
Possible cause(s)
Remedy
Device does not work
Power failure or defective
fuse
The device is defective.
Control input inverted
Check the fuses.
Have the device checked by a qualified
professional.
Check whether the control input
is correctly set.
Important: Malfunctions might occur in an unfavorable electromagnetic environment.
Caution:
Danger due to improper interventions. Do not manipulate the device.
Otherwise, this can result in function failures and device defects.