No.
Menu name
Specification
Description
13_9
Time betw.starts, P1
min:s
WritableCentral System TextTime
between starts, P1 (min:s)
Delay between two pump starts, counted from when P1 started.
13_10
Time betw.starts, P2
min:s
WritableCentral System TextTime
between starts, P2 (min:s)
Delay between two pump starts, counted from when P2 started.
13_11
Time betw.starts, P3
min:s
WritableCentral System TextTime
between starts, P3 (min:s)
Delay between two pump starts, counted from when P3 started.
13_12
Time betw.starts, P4
min:s
WritableCentral System TextTime
between starts, P4 (min:s)
Delay between two pump starts, counted from when P4 started.
13_13
Auto start intrvl. h
WritableCentral System TextAuto
start intrvl. (h)
If a pump has not been started within the set interval, the function will
start the pump for a maintenance run, The running time is set in the
Auto start time menu.
13_14
Auto start time min:s WritableCentral System TextAuto
start time (min:s)
The running time when started by the auto start function.0 - disables
the function.
13_15
High level run time
min:s
WritableCentral System TextHigh
level run time (min:s)
Backup control activated when there is a level sensor failure. The high
level switch activates the start of a pump (or two), which will then run
for the period set in this menu.
13_16
Max. run time min:s WritableCentral System TextMax.
run time (min:s)
The maximum time the pumps are allowed to run continuously. 0 -
disables the function.
13_17
Flushing interval h
Writable
Enter the number of pump cycles between each flushing
13_18
Flushing time min:s
Writable
Enter the time for which the flushing valve will be open0 - disables the
function.
14
Alarm setup...
Read only
Menu group for alarm
14_1
General alarm delay
min:s
WritableCentral System TextGeneral
alarm delay (min:s)
Delays the recording of an alarm. Used for all alarms except power
failure alarm and low level.
14_2
Pow.fail alarm delay
min
WritableCentral System TextPower
failure alarm delay (min)
The delay of a Power failure alarm before it is recorded.
14_3
Low lev. alarm delay
min:s
WritableCentral System TextLow
level alarm delay (min:s)
The delay of a Low level alarm before it is recorded.
14_4
Blocking alarm delay
min
WritableCentral System
TextBlocking alarm delay (min)
The time the blocking signal must be active before an alarm is
generated.
14_5
Work time min
Writable
Work time before an acknowledge is required from the personnel.
14_6
Warning time min
Writable
Warning time, during which an acknowledge from personnel is
requested, before the personnel alarm is sent.
14_7
Transmit alarm
Writable Alternative0 = Local1 =
Remote2 = ClearCentral System
TextTransmit alarm
Alarm transmission.0 - Local. Alarms are not transmitted.1 - Remote.
Alarms are transmitted to the Central system/SMS receiver.2 - Clear.
Clears the alarm buffer and changes to Remote.
14_8
Auto remote mode
min:s
Writable
The time after which the controller will revert to remote alarming
mode.0 - disables the function.
14_9
D-alarm start time
Writable Interval0 - 0
The start time for dialling out alarms with priority D.
14_10
D-alarm end time
Writable Interval0 - 0
The stop time for dialing out alarms with priority D.
Appendix A: RTU Descriptions
52
APP 541 User manual