Appendix A: RTU Descriptions
List of Alarms
Alarm
Code
Default
priority
Local text
SCADA System Text
Description
1
A
High level
High level
High level in pump sump. Alarm from the level sensor.
2
C
Low level
Low level
Low level in pump sump. Alarm from the level sensor.
3
B
Mains error
Mains error
The main power has been disrupted or the phase sequence is incorrect
or one phase is missing.
4
A
High level float High level float
The level in the sump reaches the high level switch. The pumps will be
started.
5
A
Pers. alarm
Personal alarm
Personal alarm warning time has run out without reset. Personnel in
danger!
11
B
Tripped motor
P1
Tripped motor protector
P1
The Pump 1 has a tripped motor protection. The pump is blocked by this
alarm.
12
B
Tripped motor
P2
Tripped motor protector
P2
The Pump 2 has a tripped motor protection. The pump is blocked by this
alarm.
13
B
Tripped motor
P3
Tripped motor protector
P3
The Pump 3 has a tripped motor protection. The pump is blocked by this
alarm.
14
B
Tripped motor
P4
Tripped motor protector
P4
The Pump 4 has a tripped motor protection. The pump is blocked by this
alarm.
15
B
High current
P1
High current P1
High current pump 1. Alarm from the analogue current measurement.
16
C
Low current P1 Low current P1
Low current pump 1. Alarm from the analogue current measurement.
17
B
High current
P2
High current P2
High current pump 2. Alarm from the analogue current measurement.
18
C
Low current P2 Low current P2
Low current pump 2. Alarm from the analogue current measurement.
19
B
High current
P3
High current P3
High current pump 3. Alarm from the analogue current measurement.
20
B
Low current P3 Low current P3
Low current pump 3. Alarm from the analogue current measurement.
21
B
High current
P4
High current P4
High current pump 4. Alarm from the analogue current measurement.
22
B
Low current P4 Low current P4
Low current pump 4. Alarm from the analogue current measurement.
27
C
Setpoint
changed
Setpoint changed
At least one menu has been changed on the local display. The alarm
reverts when new set points are sent to the RTU.
30
C
No response P1 No response P1
There is no response signal from pump 1. The pump has probably not
started despite activation of the power relay.
31
C
No response P2 No response P2
There is no response signal from pump 2. The pump has probably not
started despite activation of the power relay.
32
B
No response P3 No response P3
There is no response signal from pump 3. The pump has probably not
started despite activation of the power relay.
Appendix A: RTU Descriptions
APP 541 User manual
45