No.
Menu name
Specification
Description
2_1
Start level 1 ft
WritableCentral System TextStart
level 1 (ft)
Start level for first pump.
2_2
Stop level 1 ft
WritableCentral System TextStop
level 1 (ft)
Stop level for first pump.
2_3
Start level 2 ft
WritableCentral System TextStart
level 2 (ft)
Start level for second pump.
2_4
Stop level 2 ft
WritableCentral System TextStop
level 2 (ft)
Stop level for second pump.
2_5
Start level 3ft
WritableCentral System TextStart
level 3 (ft)
Start level for third pump.
2_6
Stop level 3 ft
WritableCentral System TextStop
level 3 (ft)
Stop level for third pump.
2_7
Start level 4 ft
WritableCentral System TextStart
level 4 (ft)
Start level for fourth pump.
2_8
Stop level 4 ft
WritableCentral System TextStop
level 4 (ft)
Stop level for fourth pump.
2_9
High level ft
WritableCentral System TextHigh
level (ft)
High level alarm limit.
2_10
Low level ft
WritableCentral System TextLow
level (ft)
Low level alarm limit.0 - disables the function
2_11
Random start range ft WritableCentral System
TextRandom start range (ft)
Random start range
2_12
Sensor range ft
WritableCentral System TextSensor
range (ft)
Sensor range.
2_13
Sensor calibration ft
WritableCentral System TextSensor
calibration (ft)
Sensor calibration offset.
3
P1 current A
Read only
Measured current for first pump.
3_1
P1 high current A
WritableCentral System TextP1 high
current (A)
High current alarm limit for first pump.
3_2
P1 low current A
WritableCentral System TextP1 low
current (A)
Low current alarm limit for first pump.
3_3
P1/P3 Current range
A
Writable
Current transformer range for pump 1
3_4
Current factor P1/P3
Writable
Current factor for P1 versus P3. Used when P1 and P3 are difference
sizes. Default is 1.0
4
P2 Current A
Read only
Measured current for second pump.
4_1
P2 high current A
WritableCentral System TextP2 high
current (A)
High current alarm limit for second pump.
4_2
P2 low current A
WritableCentral System TextP2 low
current (A)
Low current alarm limit for second pump.
4_3
Current range P2/P4
A
Writable
Current transformer range for pump 2 and 4
Appendix A: RTU Descriptions
48
APP 541 User manual