![FLYGT APP 541 User Manual Download Page 28](http://html.mh-extra.com/html/flygt/app-541/app-541_user-manual_2311478028.webp)
Menu
Values
Description
Communication
COM1
(15_10)
GPRS
The RTU will make all necessary initialization of the modem. There is no
need for any manual modem configuration.
Speed COM1
(15_13)
19200 bps
The default speed used by the modem after a power on reset.
Make sure not to configure the modem using the "AT&F" command,
since this will set the speed to 115200.
Parity COM1
(15_14)
None, Even or Odd
Use the same setting as in the communication equipment.
Protocol COM1
(15_15)
AquaCom unpolled fix
CS IP address
(15_18)
Enter the IP address to the SCADA system.
CS IP port
(15_19)
Enter the IP port of the SCADA system.
Access point 1
(15_20)
Enter the access point name. It describes the telephone provider, for
example internet.<some telephone company name\>.net.
If the name is longer than 20 characters, the name can be split in two.
Enter the first piece in the Access point 1 menu, and the second piece
in the Access point 2 menu.
Access point 2
(15_21)
Station number /
id
(15_1)
001–899
In the SCADA system, the station number is a unique number for the
RTU.
NOTICE:
If you connect a terminal to the service port in the RTU, you can specify the access point
name with the command setcomdata
.
Format: setcomdata <access point name\>
Telephone modem
Communication using a Hayes compatible telephone modem, or GSM modem.
(Reference: Observe the limitations for combinations of modems and their configuration
strings as described in the Modem Configuration manual).
Menu
Values
Description
Communication
COM1
(15_1
0)
Hayes modem
GSM/Hayes
predef.
Select Hayes modem when using TD33 for communication directly to
the SCADA system. In all other cases configure the modem using a PC
and select GSM/Hayes predefined. Select this option if an MTC-COM
is included in the system.
Speed COM1
(15_1
3)
1200-115200 bps If your modem supports autobauding, set this as high as possible to
get the best communication performances.
Otherwise set this value to the same as the value used in the pre-
configuration of the modem.
Parity COM1
(15_1
4)
None, Even or
Odd
Use the same setting as in the communication equipment.
Configure Communication
26
APP 541 User manual
Summary of Contents for APP 541
Page 1: ...APP 541 User manual Autamatic Pump Pilot APP 541 Reset Esc OK ...
Page 2: ......
Page 9: ... Reference For a detailed menu list refer to Appendix A Shortguides APP 541 User manual 7 ...
Page 74: ......