6.5.4
Program Function Mode
The next parameter is the program function or cycle mode. There are four pos-
sible modes that determine whether the program scans up (from set-point 1 to
n) only or both up and down (from set-point n to 1), and also whether the pro-
gram stops after one cycle or repeats the cycle indefinitely. Table 2 below
shows the action of each of the four program mode settings.
Pf=1
Program mode
Use the “UP” or “DOWN” buttons to change the mode.
Pf=4
New mode
Press “SET” to continue.
S
Save new setting
6.5.5
Program Control
The final parameter in the program menu is the control parameter. There are
three choices to choose from 1) start the program from the beginning, 2) con-
tinue the program from where it was when it was stopped, or 3) stop the
program.
Pr=off
Program presently off
Use the “UP” or “DOWN” buttons to change the status.
Pr=StArt
Start cycle from beginning
Press “SET” to activate the new program control command and return to the
temperature display.
S
Activate new command
29
6 Controller Operation
Ramp and Soak Program Menu
Function
Action
1
up-stop
2
up-down-stop
3
up-repeat
4
up-down-repeat
Table 2.
Program mode setting actions