Fluidwell F093-P Manual Download Page 14

 

FW-F093-P-MAN-EN_v0101_01

 

Page 14

 

CUT-OFF TIME 
25 

With this setting, you determine a minimum RPM requirement threshhold, 
if during this time less than XXX-pulses (SETUP 24) are generated, the 
engine speed will be displayed as zero.  
The cut-off time has to be entered in seconds - maximum time is 999 
seconds (about 15 minutes). 

 

 

3 - ALARM 

With these settings, it is determined how the engine speed will be monitored and the functionality of 
the transistor / relay output (terminals 7-8) be determined. 

ALARM 
31 

With this setting you determine whether the alarm system is active or not. 
The following can be selected: 

 

 

DISABLE - ENABLE 

 

RPM ZERO 
32 

When the engine speed is zero, then it is possible to ignore or disable the 
engine speed monitoring. The following settings can be selected: 
DEFAULT: 

in case of a low-engine speed alarm, it will switch the 
alarm output and indicate the alarm on the display. 

NO RELAY:  

in case of a low-engine speed alarm, it won't switch the 
alarm output but will indicate the alarm on the display 
only.  

IGNORE:  

in case of a low-engine speed alarm, it won't switch the 
alarm output and nothing will be indicated on the display. 

ALARM VALUE 
LOW ENGINE SPEED 
33 

The low alarm is set with this setting. An alarm will be generated as long 
as the engine speed is lower as this value.  
With value 0.0 this function is disabled.  

ALARM VALUE 
HIGH ENGINE SPEED 
34 

The high alarm is set with this setting. An alarm will be generated as long 
as the engine speed is higher as this value. 
With value 0.0 this function is disabled.  

DELAY TIME ALARM 
LOW ENGINE SPEED 
35 

An alarm generated by SETUP 32 “low” can be ignored during X-time 
period. If the actual engine speed is still incorrect after this delay time, 
then an alarm will be generated. 

DELAY TIME ALARM 
HIGH ENGINE SPEED 
36 

An alarm generated by SETUP 33 “high” can be ignored during X-time 
period. If the actual engine speed is still incorrect after this delay time, 
then an alarm will be generated.  

ALARM HR 
37

 

The running hours alarm is set with this setting. An alarm will be 
generated when this value of running hours is met.  
With value 0.0 this function is disabled. 

ALARM OUTPUT 
TRANSISTOR / RELAY 
38 

One transistor or relay output is available to transmit the alarm condition. 
Assign with this function the type of alarm to be transmitted: 
low engine speed alarm, high engine speed alarm or both alarms. 

 
 

4 - DISPLAY 

FUNCTION 
41 

The large 17mm digits can be set to display running hours or engine 
speed (RPM).  
When "running hours" is selected, both running hours and engine speed 
are displayed simultaneously.  
When "engine speed" is selected, only engine speed will be displayed 
with it’s measuring unit while running hours will be displayed after 
pressing SELECT. The following can be selected: 

 

 HOURS 

RPM 

 

DISPLAY 
42 

This function determines what is shown on the display. With “ALL” it will 
show both the RPM and HOURS, at “TOGGLE” it will automatically swap 
every 3 seconds between RPM and HOURS and with “HAND” you can 
manually set the display you prefer.  The following can be selected: 

 

 

ALL – TOGGLE – HAND 

 

Summary of Contents for F093-P

Page 1: ...NNING HOURS WITH ALARM OUTPUT Signal input Tachometer pulse Namur and coil Alarm output alarm on RPM and running hours Options Intrinsically Safe F Series Field mounted indicators for safe and hazardo...

Page 2: ...sed of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of your was...

Page 3: ...cedures which if not performed correctly may lead to personal injury a safety hazard or damage of the F093 P or connected instruments A caution indicates actions or procedures which if not performed c...

Page 4: ...nt 15 6 Sensor 16 7 Others 16 4 Installation 17 4 1 General directions 17 4 2 Installation surrounding conditions 17 4 3 Dimensions Enclosure 18 4 4 Installing the hardware 20 4 4 1 Introduction 20 4...

Page 5: ...re available RPM alarm output Overview typical application F093 Fig 1 Typical application for the F093 P Configuration of the unit The F093 P has been designed to be implemented in many types of appli...

Page 6: ...sers operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control Panel Functions of the keys This key is used to program and save new values or settings It is also used to gain access t...

Page 7: ...the bottom line It is possible to display engine speed only with the large 17mm digits in this instance press the SELECT key to read the running hours When is shown then the engine speed value is too...

Page 8: ...pressed yet then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER during three seconds the former value will be reinstated Engine speed alarm When the actual engine...

Page 9: ...al are to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rule...

Page 10: ...the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure the sub function Additionally each function i...

Page 11: ...lect in the other direction When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG procedure...

Page 12: ...ARM HI 0000 000 9 999 999 35 DELAY LO 0 1 999 9 seconds 36 DELAY HI 0 1 999 9 seconds 37 ALARM HR 0 9999 38 REL OUT hi lo hi lo hours off 4 DISPLAY 41 FUNCTION hours rpm 42 DISPLAY all toggle hand 43...

Page 13: ...following the decimal point The following can be selected 00000 1111 1 K FACTOR 22 With the K factor the Tachometer pulse signals are converted to an engine speed RPM The K factor is based on the num...

Page 14: ...generated as long as the engine speed is higher as this value With value 0 0 this function is disabled DELAY TIME ALARM LOW ENGINE SPEED 35 An alarm generated by SETUP 32 low can be ignored during X...

Page 15: ...red FLASH during alarm the color flashes red and the color as per setting 47 BRIGHTNESS OPTION 48 The density of the backlight can be set in following range 1 5 One is minimum and five is maximum brig...

Page 16: ...nput 20mV p t p Sensitive for disturbance COIL LO Low sensitive coil input 90mV p t p Normal sensitivity ACTIVE Active pulse input detection level 1 2V DC 47kOhm 10KHz External power required 7 OTHERS...

Page 17: ...ntal contact is no longer assured when the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained personnel Take careful n...

Page 18: ...9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24m...

Page 19: ...back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4...

Page 20: ...with the 115 230V AC power supply type PM The green yellow wire between the back casing and removable terminal block may never be removed Fig 8 Grounding aluminum enclosure with option PM 115 230V AC...

Page 21: ...terminal 6 sensor supply 8 2V With this option a basic but real sensor supply of max 5mA 8 2V is available to power e g a Namur sensor REMARKS TERMINAL CONNECTORS Terminals 1 3 Tachometer input Three...

Page 22: ...3 offers 3 2V which has to be switched by the sensor to terminal 2 SIGNAL For a reliable pulse detection the pulse amplitude has to go above 1 2V Signal setting PNP LP employs a low pass signal noise...

Page 23: ...amur signal The standard F093 P is not able to power the Namur sensor as an external power supply for the sensor is required However a 8 2V sensor supply voltage terminal 6 can be provided with type P...

Page 24: ...inal 7 8 Alarm output type OT With SETUP 36 the function of this output is set to a low and or high engine speed alarm output A passive transistor output is available with this option Max driving capa...

Page 25: ...rip s after which the internal plastic cover can be removed The switches are located on the right hand side as indicated Fig 11 switch position voltage selection type PF and PM Switch positions sensor...

Page 26: ...tive pulse or coil The screen of the signal wire must be connected to the common ground terminal The input signal type has to be selected with the correct SETUP function read par 3 2 3 Coil signal The...

Page 27: ...e detection the pulse amplitude has to go above 1 2V Signal setting PNP LP employs a low pass signal noise filter which limits the maximum input frequency read par 3 2 3 A sensor supply voltage is off...

Page 28: ...P is suitable for Tachometers with an Namur signal Terminal 7 can provide a 8 2V sensor supply voltage please read section sensor supply INTERNAL EXTERNAL Reed switch signal input 6 Common ground unit...

Page 29: ...installed in accordance with the Atex directive 94 9 EC and the product certificate KEMA 05ATEX1168 X For installation under IECEx scheme this intrinsically safe device must be installed in accordanc...

Page 30: ...applications Replace with certified FW LiBAT 00x battery only Remark consult the manual Intrinsically Safe for Class I II III Div 1 Grps A B C D E F G Temp class T4 Class I Zone 0 AEx ia IIC T4 For in...

Page 31: ...tion example Intrinsically Safe Configuration example no 2 Configuration example IIA IIB and IIC application F093 P OT PX XI ZB I S tachometer input type P pulse Backlight option type ZB not used in t...

Page 32: ...ax 30 V max 200 mA max 1 2 W Uo Io Po max 30 V max 200 mA max 0 75 W Uo Io Po Note above values are safety values Consult the technical specification for operational values Power supply For example MT...

Page 33: ...expose contents to water INSTRUCTION SHEET BATTERY REPLACEMENT FW LiBAT 001 Replacement Instructions Safety Instructions Fluidwell bv The Netherlands www fluidwell com sales fluidwell com FW LiBAT 00...

Page 34: ...t no condensation will occur for example by placing dry silica gel sachet in the casing just before closing it Furthermore it is required to replace or dry the silica gel periodically as advised by th...

Page 35: ...HJ Type HH Type HK ABS enclosure Type HS Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 NEMA4X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling 1x M20 Drilling 2x M20 Drilling 6x M12...

Page 36: ...AEx ia IIC T4 Explosion proof Type XF ATEX approval ref EX II 2 GD EEx d IIB T5 Weight appr 15kg Dimensions of enclosure 350 x 250 x 200mm 13 7 x 9 9 x 7 9 LxHxD Environment Electromagnetic compatibil...

Page 37: ...ts hours Decimals 0 or 1 Note running hours can be reset to zero Accumulated running hours Digits 11 digits Units decimals according to selection for running hours Engine speed RPM Digits 7 digits Uni...

Page 38: ...and time unit correct SETUP 26 27 The unit has to count the number of pulses according to SETUP 26 within the time according to SETUP 27 Make sure that 27 is set to 10 0 seconds for example the result...

Page 39: ...upply voltage 21 24 25 serial number 16 setup level 9 software version 3 subfunction 10 tachometer signal 16 tachometer input 21 26 tagnumber 16 technical specification 35 terminal connectors 21 24 ve...

Page 40: ...0 38 alarm output hi lo 4 DISPLAY 41 function rpm 42 display all 43 clr hrs operate 44 alarm set operate 45 acc hours hide 46 backlight green 47 bl alarm off 48 brightness 5 5 POWER MANAGEMENT 51 LCD...

Reviews: