FW-F093-P-MAN-EN_v0101_01
Page 14
CUT-OFF TIME
25
With this setting, you determine a minimum RPM requirement threshhold,
if during this time less than XXX-pulses (SETUP 24) are generated, the
engine speed will be displayed as zero.
The cut-off time has to be entered in seconds - maximum time is 999
seconds (about 15 minutes).
3 - ALARM
With these settings, it is determined how the engine speed will be monitored and the functionality of
the transistor / relay output (terminals 7-8) be determined.
ALARM
31
With this setting you determine whether the alarm system is active or not.
The following can be selected:
DISABLE - ENABLE
RPM ZERO
32
When the engine speed is zero, then it is possible to ignore or disable the
engine speed monitoring. The following settings can be selected:
DEFAULT:
in case of a low-engine speed alarm, it will switch the
alarm output and indicate the alarm on the display.
NO RELAY:
in case of a low-engine speed alarm, it won't switch the
alarm output but will indicate the alarm on the display
only.
IGNORE:
in case of a low-engine speed alarm, it won't switch the
alarm output and nothing will be indicated on the display.
ALARM VALUE
LOW ENGINE SPEED
33
The low alarm is set with this setting. An alarm will be generated as long
as the engine speed is lower as this value.
With value 0.0 this function is disabled.
ALARM VALUE
HIGH ENGINE SPEED
34
The high alarm is set with this setting. An alarm will be generated as long
as the engine speed is higher as this value.
With value 0.0 this function is disabled.
DELAY TIME ALARM
LOW ENGINE SPEED
35
An alarm generated by SETUP 32 “low” can be ignored during X-time
period. If the actual engine speed is still incorrect after this delay time,
then an alarm will be generated.
DELAY TIME ALARM
HIGH ENGINE SPEED
36
An alarm generated by SETUP 33 “high” can be ignored during X-time
period. If the actual engine speed is still incorrect after this delay time,
then an alarm will be generated.
ALARM HR
37
The running hours alarm is set with this setting. An alarm will be
generated when this value of running hours is met.
With value 0.0 this function is disabled.
ALARM OUTPUT
TRANSISTOR / RELAY
38
One transistor or relay output is available to transmit the alarm condition.
Assign with this function the type of alarm to be transmitted:
low engine speed alarm, high engine speed alarm or both alarms.
4 - DISPLAY
FUNCTION
41
The large 17mm digits can be set to display running hours or engine
speed (RPM).
When "running hours" is selected, both running hours and engine speed
are displayed simultaneously.
When "engine speed" is selected, only engine speed will be displayed
with it’s measuring unit while running hours will be displayed after
pressing SELECT. The following can be selected:
HOURS
-
RPM
DISPLAY
42
This function determines what is shown on the display. With “ALL” it will
show both the RPM and HOURS, at “TOGGLE” it will automatically swap
every 3 seconds between RPM and HOURS and with “HAND” you can
manually set the display you prefer. The following can be selected:
ALL – TOGGLE – HAND