User Manual
E126-P-EL
Page 68
FW_E126-P-EL_M_v0301-01_EN
MODBUS-REGISTERS: OTHERS
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 160
[h] 0x0A0
40161
model number
1
R
uint16 0…9999
[d] 173
[h] 0x0AD
40174
model suffix
1
R
char
Representation: ASCII character
[d] 162
[h] 0x0A2
40163
firmware
version
2
R
uint32 0…999999
Representation: xx.xx.xx
[d] 165
[h] 0x0A5
40166
serial number
2
R
uint32 0…9999999
Representation: xxxxxxx
[d] 176
[h] 0x0B0
40177
local time
2
R/W
uint32 00:00:00…23:59:59
Representation: hh:mm:ss
Stored decimal: 23:59:59 = 235959d = 0x0003.99B7
[d] 168
[h] 0x0A8
40169
password
1
R
uint16 0…9999
[d] 139
[h] 0x08B
40140
keyboard lock
1
R/W
uint16 0=disable
1=enable
[d] 170
[h] 0x0AA
40171
tag number
2
R/W
uint32 0…9999999
Representation: xxxxxxx