MODBUS-REGISTERS: ANALOG OUTPUT
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 112
[h] 0x070
40113
analog output
1
R/W
uint16 0=disable
1=enable
[d] 113
[h] 0x071
40114
minimum rate
2
R/W
uint32 0.001…9999999
Representation: unit, time, decimals depending on variables
48, 49, 50
[d] 116
[h] 0x074
40117
maximum rate
2
R/W
uint32 0.001…9999999
Representation: unit, time, decimals depending on variables
48, 49, 50
[d] 119
[h] 0x077
40120
cut-off
percentage
1
R/W
uint16 0…99
Representation: 0.0…9.9%
[d] 120
[h] 0x078
40121
tune minimum
output
1
R/W
uint16 0…9999
[d] 122
[h] 0x07A
40123
tune maximum
output
1
R/W
uint16 0…9999
[d] 127
[h] 0x07F
40128
filter
1
R/W
uint16 0…99
MODBUS-REGISTERS: PULSE OUTPUT
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 141
[h] 0x08D
40142
pulse mode
1
R/W
uint16 0=disable
1=scaled
2=retrans
[d] 128
[h] 0x080
40129
pulse time width
1
R/W
uint16 0…9999
Representation: 0.001…9.999sec
[d] 130
[h] 0x082
40131
pulse per X
quantity
2
R/W
uint32 1…9999999
Representation: 0.000001…9999999 depending on variable
133
[d] 133
[h] 0x085
40134
pulse quantity
decimals
1
R/W
uint16 0…3
MODBUS-REGISTERS: MODBUS COMMUNICATION
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 144
[h] 0x090
40145
speed
(baudrate)
1
R/W
uint16 0=1200
1=2400
2=4800
3=9600
4=9600HP
5=19200
6=38400
[d] 145
[h] 0x091
40146
modbus
address
1
R/W
uint16 1…247
[d] 146
[h] 0x092
40147
modbus mode
1
R/W
uint16 0=off
1=RTU
2=ASCII
[d] 1271
[h] 0x4F7
41272
data bits
1
R/W
uint16 0=7bit
1=8bit
[d] 1272
[h] 0x4F8
41273
parity
1
R/W
uint16 0=none
1=even
2=odd
[d] 147
[h] 0x093
40148
delay
1
R/W
uint8 0…255ms
delay between receiving a (valid) modbus command and
sending the response
[d] 150
[h] 0x096
40151
index
1
R/W
uint16 0…255
used for indexed values
[d] 149
[h] 0x095
40150
index use
1
R/W
uint16 0=static
1=auto
increment
2=auto
decrement
[d] 25
[h] 0x019
40026
reboot
1
R/W
uint16 Returns 0 on read
Write 0xA50F for unit restart
Write 0x5AF0 for factory settings