Installation  

Step Four 

 

The FT10 series flow switch must always be in contact with the 
liquid being measured. The GT10 series flow switch must never 
be submersed in liquid. 

Both flow switches feature a 3/4” NPT 

threads  which  will  allow  it  to  be  used  with  various  types  of 
fittings.  Be  sure  to  check  the  insertion  depth  of  the  flow 
switch in the fitting after it is installed. See the diagram to the 
right for the recommended insertion depth.  

 

The two tip of the sensor are to be perpendicular to 
the flow (as seen to the right).  Never mount the tips 
with one in from t of the other. 

 

When using any type of fitting, the orientation as well as the 
insertion  depth  of  the  flow  switch  in  the  pipe  is  critical.  See 
the  diagram  to  the  right  for  the  recommended  orientation.  
Best location for installation will be along the top of the pipe. 

 

 

Warning

 

 

The flow switch tips have a thin plastic wall which may be damaged if dropped or installed improperly. 

 

The FT10 flow switch is designed for use in liquid. For best results, avoid installing the FT10 where bubbles 
are present or where the tips of the switch may be out of the liquid. 

 

The  GT10  flow  switch  is  designed  for  us  in  gas  applications.  For  best  results,  avoid  installing  the  GT10 
where it may be submersed in liquid.  

 

Always  install  the  Viton  gasket  with  all  versions  of  the  FT10‐__2_.  The  G  threaded  version  will  not  seal 
unless the gasket is properly installed.  

 

The  two  temperature  probes  (tips)  must  always  be  perpendicular  to  the  flow  (see  the  flow  at  the  same 
time). 

 

 

Summary of Contents for Thermo-Flow 5405

Page 1: ...1 F herm Dispe 10 GT1 Flo 10500 H Los Alam Tel 5 Fax 5 www FT900003 mo F ersion 10 Series owline Inc Humbolt Str mitos CA 90 562 598 301 562 431 850 w flowline com Flo Flow S s Manua reet 0720 15 07 m...

Page 2: ...t applied in applications with relatively constant temperatures New Features Rugged Polypropylene Ryton or PVDF sensor for corrosive liquids and gasses Adjustable set point with LED for flow or no flo...

Page 3: ...40 to 60 Pressure 150 psi 10 bar 25 C derated 1 667 psi 113 bar per C Above 25 C Sensor rating NEMA 4X IP65 Sensor Material 1_ _5 PP Ryton 5_ _5 PVDF Cable jacket mat 1_ _5 PP 5_ _5 FEP Cable type 4...

Page 4: ...on Polypropylene R x G FT10 5305 Short 3 PVDF FEP NPT x NPT FT10 5325 Short 3 PVDF FEP R x R FT10 5405 Long 4 5 PVDF FEP NPT x NPT FT10 5425 Long 4 5 PVDF FEP R x G Configurations Gas Flow Switches Pa...

Page 5: ...g beyond a maximum of 80 inch pounds torque Always check for leaks prior to system start up Material Compatibility The FT10 and GT10 series sensors are available in two different wetted materials Mode...

Page 6: ...Thermo Flo flow switches have no moving parts to clog or foul making them suitable for a verity of applications including non coating and non scaling liquids The FT10 series directly measure mass flow...

Page 7: ...insertion depth of the flow switch in the pipe is critical See the diagram to the right for the recommended orientation Best location for installation will be along the top of the pipe Warning The flo...

Page 8: ...e wire stripper carefully remove the outer layer of insulation from the last 1 1 4 of the sensor s cable Unwrap and discard the exposed foil shield from around the signal wires leaving the drain wire...

Page 9: ...egative The Load can be attached to either the Green or White wires Complete the circuit by connecting the Green to VDC power or White to VDC power see illustration to the right Switching a Normally O...

Page 10: ...jumping to the Black wire while the White wire is connected to the LOAD Jumper the LOAD back to the Negative to complete the circuit Normally Open DC Load as a N Channel Output Open during Flow Close...

Page 11: ...iometer The adjustment is a single turn 270 potentiometer The initial response time of the flow switch after adjustment is 1 to 10 seconds Adjust the potentiometer in slow increments and wait for the...

Page 12: ...of installation as outlined in the installation section of this manual Testing the Sensor FT10 Series Only 1 Immersing the switch Place the switch in a cup of water Make sure the tips are submersed i...

Page 13: ...OFF flow condition b Place the sensor on the table and place the cup over the sensor and let it rest waiting for the Red LED to turn ON again no flow condition c Repeat the above two steps 4 Relay Te...

Page 14: ...procedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service pers...

Reviews: