CALIBRATION  

Step Eight 

Set Point:  

If the preset factory calibration is not adequate for your application, follow the calibration steps 

listed below. 

Note: 

The  switch’s  internal  LED  will  be  on  when  the  switch  detects  no‐flow  and  will  off  when  the  switch 

detects  flow,  regardless  of  the  polarity  of  the  Red  and  Black  wires.    Reversing  the  Red  and  Black  wires  will 
reverse the polarity of the relay switch, but not the internal LED.    

1.

 

Install  the  fitting  and  flow  switch  as  described  in  the  Installation  section  of  this  manual.  Turn  the  flow 
switch  and  controller  power  on  and  adjust  the  flow  rate  to  the  application  setting.  If  the  medium  to  be 
sensed is likely to be subject to any temperature variation, the flow switch should be set as the highest 
normal temperature likely to be encountered. 

2.

 

Locate  the  potentiometer  knob  at  the  top  of  the  flow  switch.  The  red  LED  is  visible  through  the 
potentiometer.  The adjustment is a single turn 270° potentiometer. The initial response time of the flow 
switch after adjustment is 1 to 10 seconds. Adjust the potentiometer in slow increments and wait for the 
response. 

a.

 

LED is ON ‐ If the LED is on, slowly adjust the potentiometer counter‐clockwise, with a small flat head 
screwdriver until the LED turn off. 

b.

 

LED  is  OFF  ‐  If  the  LED  is  off,  slowly  adjust  the  potentiometer  clockwise.  with  a  small  flat  head 
screwdriver until the light turns on.  

3.

 

Adjust the potentiometer back and forth where the LED is switching, eventually settling for where the LED 
is OFF (this is the low flow state for the switch). 

a.

 

If the flow is increased, the LED will remain OFF indicating a flow condition 

b.

 

If the flow is decrease, the LED will turn ON indicating a no‐flow condition.   

4.

 

Verify that the new calibration is correct by lowering the system flow rate below the set point and check to 
see that the red LED turns on. Then increase the flow rate above the set point and verify that the red LED 
turns off accordingly. 

FT10 Flow Switch  

(Liquid Only) 

Potentiometer 

Location 

GT10 Flow Switch  

(Gas Only)

 

 

 

 

Summary of Contents for Thermo-Flow 5405

Page 1: ...1 F herm Dispe 10 GT1 Flo 10500 H Los Alam Tel 5 Fax 5 www FT900003 mo F ersion 10 Series owline Inc Humbolt Str mitos CA 90 562 598 301 562 431 850 w flowline com Flo Flow S s Manua reet 0720 15 07 m...

Page 2: ...t applied in applications with relatively constant temperatures New Features Rugged Polypropylene Ryton or PVDF sensor for corrosive liquids and gasses Adjustable set point with LED for flow or no flo...

Page 3: ...40 to 60 Pressure 150 psi 10 bar 25 C derated 1 667 psi 113 bar per C Above 25 C Sensor rating NEMA 4X IP65 Sensor Material 1_ _5 PP Ryton 5_ _5 PVDF Cable jacket mat 1_ _5 PP 5_ _5 FEP Cable type 4...

Page 4: ...on Polypropylene R x G FT10 5305 Short 3 PVDF FEP NPT x NPT FT10 5325 Short 3 PVDF FEP R x R FT10 5405 Long 4 5 PVDF FEP NPT x NPT FT10 5425 Long 4 5 PVDF FEP R x G Configurations Gas Flow Switches Pa...

Page 5: ...g beyond a maximum of 80 inch pounds torque Always check for leaks prior to system start up Material Compatibility The FT10 and GT10 series sensors are available in two different wetted materials Mode...

Page 6: ...Thermo Flo flow switches have no moving parts to clog or foul making them suitable for a verity of applications including non coating and non scaling liquids The FT10 series directly measure mass flow...

Page 7: ...insertion depth of the flow switch in the pipe is critical See the diagram to the right for the recommended orientation Best location for installation will be along the top of the pipe Warning The flo...

Page 8: ...e wire stripper carefully remove the outer layer of insulation from the last 1 1 4 of the sensor s cable Unwrap and discard the exposed foil shield from around the signal wires leaving the drain wire...

Page 9: ...egative The Load can be attached to either the Green or White wires Complete the circuit by connecting the Green to VDC power or White to VDC power see illustration to the right Switching a Normally O...

Page 10: ...jumping to the Black wire while the White wire is connected to the LOAD Jumper the LOAD back to the Negative to complete the circuit Normally Open DC Load as a N Channel Output Open during Flow Close...

Page 11: ...iometer The adjustment is a single turn 270 potentiometer The initial response time of the flow switch after adjustment is 1 to 10 seconds Adjust the potentiometer in slow increments and wait for the...

Page 12: ...of installation as outlined in the installation section of this manual Testing the Sensor FT10 Series Only 1 Immersing the switch Place the switch in a cup of water Make sure the tips are submersed i...

Page 13: ...OFF flow condition b Place the sensor on the table and place the cup over the sensor and let it rest waiting for the Red LED to turn ON again no flow condition c Repeat the above two steps 4 Relay Te...

Page 14: ...procedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service pers...

Reviews: