Low-Flow Cutoff (
cutF
)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 9999. Below the cutoff
value, the meter will display zero. Programming the cutoff value to zero
disables the cutoff.
cutF
Set Cutoff
Value
Func
0
3
.00
SELc
Press Enter to Accept Setting
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
Advanced
Features
out
Display Intensity (
inty
)
The Display Intensity function allows the selection of eight levels of in-
tensity for various lighting conditions.
inty
Select Display
Intensity Level
Func
int3
SELc
Press Enter to Accept Setting
Press Up to Select Value
Press Menu to Exit at any Time
Advanced
Features