LI5X Process & Temperature Meter Instruction Manual
44
Scaling the Meter (
scal
)
The process inputs (4-20 mA and
±
10 VDC) can be scaled to display
the process in engineering units.
A signal source is not needed to scale the meter; simply program the
inputs and corresponding display values.
dis1
0
0
.0
Press Enter to Accept Setting
inp2
Scale
Input 2
inp1
Set Input 1
Value
scal
0
4.00
Set Display 1
Value
Press Up to Set Digit Value
Press Right to Select Next Digit
Press Menu to Exit at any Time
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 28.
Note:
The
Scale
menu is not available for temperature inputs.