![FlowLine LI50-1001 Instruction Manual Download Page 37](http://html1.mh-extra.com/html/flowline/li50-1001/li50-1001_instruction-manual_2308219037.webp)
LI5X Process & Temperature Meter Instruction Manual
37
Time Delay Operation
The following graphs show the operation of the time delay function.
Set
Reset
Relay
LED
*
Input
On Time Delay
<Tdelay
<Tdelay
>=Tdelay
Set
Reset
Relay
Input
Off Time Delay
<Tdelay
<Tdelay
>=Tdelay
LED
*
If the signal crosses the set point, the
On
time delay timer starts and the
relay trips when the time delay has elapsed. If the signal drops below
the set point (high alarm) before the time delay has elapsed, the
On
time delay timer resets and the relay does not change state. The same
principle applies to the
Off
time delay.
* Note: The LED is not affected by Time Delay when
“Automatic or
Manual”
reset mode is selected. Rather the LED follows the set
and reset points.