FlowLine DataPoint LC52 Series Manual Download Page 6

6

 

of

 

18

 

LC900007

 

Rev

 

A2

 

GETTING

 

STARTED

 

Step

 

Four

 

Features

 

of

 

a

 

Single

 

Input

 

High

 

or

 

Low

 

Relay:

  

Single

 

Input

 

Relays

 

(Relay

 

1

 

or

 

Relay

 

2

 

w/

 

latch

 

turned

 

OFF)

 

are

 

designed

 

to

 

switch

 

from

 

a

 

single

 

set

point.

  

It

 

turns

 

its

 

internal

 

relay

 

ON

 

or

 

OFF

 

(as

 

set

 

by

 

the

 

invert

 

switch)

 

in

 

response

 

to

 

the

 

presence

 

of

 

liquid,

 

and

 

changes

 

the

 

relay

 

status

 

back

 

again

 

when

 

the

 

sensor

 

is

 

dry.

   

High

 

Alarm:

   

Invert

 

is

 

OFF.

  

Relay

 

will

 

energize

 

when

 

the

 

level

 

rises

 

above

 

the

 

high

 

alarm

 

setting

 

and

 

will

 

de

energize

 

when

 

it

 

drops

 

below

 

the

 

high

 

alarm

 

setting.

 

Low

 

Alarm:

  

Invert

 

is

 

ON.

  

Relay

 

will

 

energize

 

when

 

the

 

level

 

drops

 

below

 

the

 

low

 

alarm

 

setting

 

and

 

will

 

de

energize

 

when

 

it

 

rises

 

above

 

the

 

low

 

alarm

 

setting.

 

Single

 

input

 

high

 

or

 

low

 

relays

 

may

 

be

 

used

 

with

 

any

 

device

 

that

 

outputs

 

a

 

4

20

 

mA

 

signal.

  

The

 

relay

 

is

 

a

 

single

 

pole,

 

double

 

throw

 

type;

 

the

 

controlled

 

device

 

can

 

be

 

connected

 

to

 

either

 

the

 

normally

 

open

 

or

 

normally

 

closed

 

side

 

of

 

the

 

relay.

  

A

 

time

 

delay

 

from

 

0.15

 

to

 

60

 

seconds

 

can

 

be

 

set

 

before

 

the

 

relay

 

responds

 

to

 

the

 

sensor

 

input.

  

Typical

 

applications

 

for

 

single

 

input

 

relays

 

are

 

high

 

level

 

or

 

low

 

level

 

switch/alarm

 

operations

 

(opening

 

a

 

drain

 

valve

 

whenever

 

liquid

 

level

 

rises

 

to

 

a

 

set

point)

 

and

 

over

flow

 

protection

 

(turning

 

off

 

a

 

pump

 

or

 

sounding

 

an

 

alarm

 

when

 

a

 

high

 

level

 

is

 

reached).

   

Features

 

of

 

a

 

Latching

 

Relay

 

(automatic

 

fill

 

or

 

empty):

  

The

 

latching

 

relay

 

(relay

 

2

 

only)

 

is

 

designed

 

to

 

switch

 

a

 

relay

 

on

 

and

 

off

 

at

 

two

 

different

 

levels.

  

It

 

turns

 

its

 

internal

 

relay

 

ON

 

or

 

OFF

 

(as

 

set

 

by

 

the

 

invert

 

switch)

 

in

 

response

 

when

 

the

 

level

 

is

 

above

 

the

 

high

 

setting

 

or

 

below

 

the

 

low

 

setting.

  

The

 

relay

 

will

 

not

 

change

 

its

 

state

 

when

 

the

 

level

 

is

 

between

 

the

 

high

 

and

 

low

 

setting.

   

Automatic

 

Empty:

 

Latch

 

is

 

ON

 

&

 

Invert

 

is

 

OFF.

  

Relay

 

will

 

energize

 

when

 

level

 

reaches

 

high

 

setting

 

(both

 

settings

 

are

 

submersed).

  

Relay

 

will

 

de

energize

 

when

 

level

 

is

 

below

 

the

 

bottom

 

setting

 

(both

 

settings

 

are

 

dry).

 

Automatic

 

Fill:

 

Latch

 

is

 

ON

 

&

 

Invert

 

is

 

ON.

   

Relay

 

will

 

energize

 

when

 

level

 

is

 

below

 

the

 

bottom

 

setting

 

(both

 

switches

 

are

 

dry).

   

Relay

 

will

 

de

energize

 

when

 

level

 

is

 

above

 

the

 

high

 

setting

 

(both

 

settings

 

are

 

wet).

  

 

 

Summary of Contents for DataPoint LC52 Series

Page 1: ...Rev A2 LC900007 1 of 18 DataPoint Continuous Relay Controller LC52 Series Manual CALL TOLL FREE 877 742 2878 FOR SALES AND SUPPORT CLICK HERE TO RETURN TO WEBSITE ...

Page 2: ...its Fail Safe relay control of pumps valves or alarms with a 0 15 to 60 second delay Polypropylene enclosure can be DIN rail mounted or back panel mounted Easy setup with push button calibration for display and relay settings AC powered Table of Contents Specifications 3 Dimensions 3 Safety Precautions 4 Make a Fail Safe System 5 Components 5 Installation 5 Getting Started 6 Features of the Single...

Page 3: ...VDC 25mA primary 28 VDC 50mA secondary Contact type 1 SPDT 1 Latched SPDT Contact rating 250 VAC 12A Hp Contact output Selectable NO or NC Contact latch ON or OFF Contact configuration 1 High or low level alarm 2 High and low level alarm 3 Automatic fill or empty 4 Automatic fill or empty with alarm Contact delay 0 15 60 seconds Fail safety Power fail safe Repeater output 4 20 mA 12 36 VDC Ambient...

Page 4: ...al electrical codes Flammable or Explosive Applications The LC52 series continuous relay controllers should not be used with explosive or flammable liquids which require an intrinsically safe or explosion proof rating If you are unsure of the suitability of a controller for your installation consult your Flowline representative for further information Install In a Dry Location The controller housi...

Page 5: ...contact so that it will not complete the circuit when it should In critical applications redundant backup systems and alarms must be used in addition to the primary system Such backup systems should use different sensor technologies where possible While this manual offers some examples and suggestions to help explain the operation of FLOWLINE products such examples are for information only and are...

Page 6: ...lay from 0 15 to 60 seconds can be set before the relay responds to the sensor input Typical applications for single input relays are high level or low level switch alarm operations opening a drain valve whenever liquid level rises to a set point and over flow protection turning off a pump or sounding an alarm when a high level is reached Features of a Latching Relay automatic fill or empty The la...

Page 7: ... amps for reactive loads the current must be derated or protection circuits used When the red LED is ON and the relay is in the energized state the NO terminal will be closed and the NC terminal will be open 5 Invert switch This switch reverses the logic of the relay control in response to the switch es conditions that used to energize the relay will now de energize the relay and vice versa 6 Time...

Page 8: ...quick review of wiring the LC52 series to common 4 20 mA transmitters EchoSonic II LU23 LU27 LU28 LU29 series EchoPod DL10 DL14 DL24 DL34 series Sourcing mode Factory Setting EchoSpan LU80 LU81 LU83 LU84 series Sourcing Mode Factory Setting Echotouch LU30 5004 and LU30 5064 only Sourcing Mode Factory Setting Echotouch LU30 5003 and LU30 5063 only Sinking mode internal jumper must be changed DeltaS...

Page 9: ...urcing to sinking remove jumper from JWA and place on JWB The LC52 is shipped from the factory in the sourcing mode JWA active 4 Gently return PCB into housing and replace back panel Note Loop powered devices can operate in either the souring or sinking modes Sourcing Mode Sinking Mode No Change Required EchoSonic II LU23 LU27 LU28 LU29 series EchoSpan LU80 LU81 LU83 LU84 series EchoPod DL10 DL14 ...

Page 10: ...uit board PCB from the housing Use caution when removing the PCB 2 Locate jumpers JW1 JW2 and JW3 on the PCB 3 To change from 120 VAC to 240 VAC a Remove the jumpers from JW1 JW2 and add a jumper to JW3 4 To change from 240 VAC to 120 VAC a Remove the jumper from JW3 and add jumpers to JW1 JW2 5 Gently return PCB into housing and replace back panel 120 VAC Jumper Setting 240 VAC Jumper Setting Rel...

Page 11: ...ower supply or some other indicator or backup alarm to warn of a power failure in the alarm circuit In this application the normal status of the relay set point at the bottom of the tank will be wet and the relay will be energized holding the alarm circuit open The relay LED will be ON so for this application Invert should be set to the OFF position High Level Alarm In the same manor this system c...

Page 12: ...hould open starting to fill the tank When the liquid is above the low relay set point the valve will remain open When the liquid reaches the high relay set point the valve should close Latch In any 2 setpoint relay configuration LATCH must be ON Invert Referring to the logic chart in Step Nine we look for the setting that will de energize the relay valve close when both relay set points are wet In...

Page 13: ...bar graph will jump one Green bar to the right next to RLY2A 8 Use UP DWN buttons to change display to the desired RLY2A value 9 Press the SET button again Immediately the LED bar graph will jump one Green bar to the right next to RLY2B 10 Use UP DWN buttons to change display to the desired RLY2B value 11 Press the SET button again Immediately the LED bar graph will return back to it normal operat...

Page 14: ...mpty with latch ON With Latch OFF the relay will only respond to the RLY 2A relay set point RLY 2B will be ignored With Latch OFF the setting for RLY 2B will be ignored All changes to the relay s state will occur from the RLY 2A relay set point Invert OFF Latch OFF RLY 2A RYL 2B Relay Wet Dry No Effect No Effect ON OFF Invert ON Latch OFF RLY 2A RYL 2B Relay Wet Dry No Effect No Effect OFF ON With...

Page 15: ...A Check for loose or open wires between the transmitter and LC52 and check the output of the transmitter Bar Graph shows a single Red bar This indicates a current input greater than 20mA Remove power immediately Check for a short in the wiring between the transmitter and LC52 or for some other power source that is affecting the input loop RLY 2B does not appear Flip Latch switch to ON Relay switch...

Page 16: ...e LC52 1001 OFFSET 0 0 SPAN 60 0 RLY 1 55 0 RLY 2A 50 0 RLY 2B 10 0 The next exercise demonstrates the same inventory control with automatic filling and a high level alarm However the units have been changes from inches to gallons Within the tank 1 50 gallons of liquid The usable range is now 300 gallons of liquid The pump starts filling at 50 gallons of liquid and stops filling at 250 gallons of ...

Page 17: ...C52 1001 OFFSET 16 0 SPAN 56 0 RLY 1 50 0 RLY 2A 20 0 RLY 2B N A The next exercise demonstrates the same inventory control with a high and low level alarm However the units have been changes from inches to gallons Along the straight side of the tank 1 50 gallons of liquid The usable range is now from 50 to 250 gallons of liquid The high level alarm occurs at 220 gallons of liquid The low level ala...

Page 18: ...ocedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilateral...

Reviews: