Rev
A2
LC900007
15
of
18
APPENDIX
(continued)
Step
Nine
Lock
Out
Function:
The
buttons
on
the
face
of
the
LC52
series
can
be
disengaged
or
locked
out.
To
lockout
the
buttons,
press
both
delay
buttons
and
the
DWN
button
simultaneously
(see
below
left).
This
will
lockout
all
of
the
buttons
and
prevent
an
accidental
changing
of
settings.
To
unlock
the
buttons,
press
both
delay
buttons
and
the
UP
button
simultaneously
(see
below
right).
Lock
Out
ON
(LOCKED)
Lock
Out
OFF
(UNLOCKED)
Troubleshooting
PROBLEM
SOLUTION
Display
is
not
reading
correct
level.
First
check
the
Bar
Graph
to
make
sure
it
is
indicating
the
correct
level.
If
not,
check
transmitter.
If
so,
perform
a
factory
reset
on
the
LC52
and
reset
values.
Bar
Graph
is
not
indicating
the
correct
level.
Check
the
transmitter’s
4
‐
20
mA
output
making
sure
it
is
spanned
correctly
for
the
application.
Bar
Graph
shows
a
single
Amber
bar.
This
indicates
a
current
input
less
than
4mA.
Check
for
loose
or
open
wires
between
the
transmitter
and
LC52
and
check
the
output
of
the
transmitter.
Bar
Graph
shows
a
single
Red
bar.
This
indicates
a
current
input
greater
than
20mA.
Remove
power
immediately.
Check
for
a
short
in
the
wiring
between
the
transmitter
and
LC52
or
for
some
other
power
source
that
is
affecting
the
input
loop.
RLY
2B
does
not
appear.
Flip
Latch
switch
to
ON.
Relay
switches
only
from
RLY
2A
(ignores
RLY
2B).
Latch
is
turned
OFF.
Flip
the
latch
switch
to
turn
ON.
Level
reaches
alarm
ON,
but
relay
is
OFF.
First,
check
to
make
sure
the
input
LED
is
ON.
If
not,
check
wiring
to
sensor.
Second,
check
status
of
Relay
LED.
If
incorrect,
flip
the
Invert
switch
to
change
the
relay
state.
Pump
or
Valve
is
supposed
to
stop,
but
it
does
not.
First,
check
to
make
sure
the
bar
graph
is
indicating
the
correct
level.
Next
check
the
relay
settings.
Finally,
check
status
of
Relay
LED.
If
incorrect,
flip
the
Invert
switch
to
change
the
relay
state.
Controller
is
powered,
but
nothing
happens.
First
check
the
Power
LED
to
make
sure
it
is
Green.
If
not,
check
the
wiring,
power
and
make
sure
the
terminal
is
seated
correctly.