www.flowair.com |3
1. GENERAL INFORMATION
Purpose of Eils B is to minimalize heat losses (or unwanted
heat gains) by door openings. Elis B is a recessed type and
can be a part suspended ceiling.
ELiS types:
ELIS B-W-100
– curtain with water heat exchanger max. range
5 m;
ELIS B-N-100
– curtain without heat exchanger (ambient);
max. range 5 m;
ELIS B-E-100
– curtain with electrical heat exchanger max.
range 5 m;
ELIS B-W-150
– curtain with water heat exchanger max. range
5 m;
ELIS B-N-150
– curtain without heat exchanger (ambient);
max. range 5 m;
ELIS B-E-150
– curtain with electrical heat exchanger max.
range 5 m,
ELIS B-W-200
– curtain with water heat exchanger max. range
5 m;
ELIS B-N-200
– curtain without heat exchanger (ambient);
max. range 5 m.
ELIS B-E-200
– curtain with electrical heat exchanger max.
range 5 m,
2. TECHNICAL DATA
B-W-
100
B-N-
100
B-E-
100
B-W-
150
B-N-
150
B-E-
150
B-W-
200
B-N-
200
B-E-
200
Power supply [V/Hz]
230 / 50
3x400 /
50
230 / 50
3x400 /
50
230 / 50
3x400 /
50
Power consumption [kW]
0,34
0,42
7,5
0,36
0,44
11,5
0,38
0,49
15,5
Current consumption [A]
1,5
1,9
11
1,6
2
16,6
1,7
2,2
22,4
IP / Insulation class
21 / F
Connecting stub [”]
½
-
½
-
½
-
Max. water temperature [
o
C]
95
-
95
-
95
-
Max. water pressure [MPa]
1,6
-
-
1,6
-
-
1,6
-
-
Temperature increase (
∆
T) [ºC]*
15
-
11
15
-
12
16
-
13
Weight [kg]
32,3
31,7
34,5
41,2
38,9
42,4
50
47,2
53,2
Weight of unit filled with water
[kg]
33,1
-
-
42,4
-
-
51,6
-
-
* B-W temperature increase at inlet air 10C and heating agent temperature 90/70C / A-E temperature increase at inlet air 10ºC
2.1. CONSTRUCTION
§
Fan
–
motor with plastic rotor;
§
Heat exchanger
– copper-aluminium, connecting stub
½
”; electrical heaters PTC;
§
Casing
– sheet steel RAL; color white RAL 9016,
–
back elements - expanded polypropylene EPP; colour - grey
–
air inlet fins - anodized aluminum