5.   CONTROL SYSTEMS 

DRV CONTROL

§

  Connecting curtains – controlling up to 5 units with one controller;

 

§

  Connecting to curtain room thermostat*, door contact*, valves with actuator*, speed controller*;

 

§

  BMS connection;

 

*optional equipment

 

5.1. CONTROL ELEMENTS 

 

TS - 3-speed fan switch with 
room thermostat  

Temperature range:: 
 +10 

 +30

o

Operatiing temperature range: 

 +40

o

IP/Insulation class:: IP30 
Max current: 
inductive 5A, resistive 6A 
Power supply: 230V/50Hz 

 

 

T-box 

 

Temperature range:: 
 +5 

 +35

o

Operating temperature 
range: -10 

 +60

o

IP/Insulation class: IP30 
Power supply: 24VDC 

 

 

DCm – mechanical door contact 

Operating temperature range::  -10 -
+80

 o

IP/Insulation class: IP 65 
Connectors: 1xNC i 1xNO 
Max current: 
resistive 10A – inductive 3A 
Max Power load: 300Vac  or  
250Vdc 

 

 

DCe – magnetic door 
contact 

Operating temperature 
range:: 
-5 - +60 

o

IP/Insulation class: IP 64 
Connectors: NC 
Max current:: 
inductive/resistive 0,5A 
Max power Load: 175Vdc 
Lenght of cabel: 2m 
Max operating contactors 
distance: 8mm 

 

 

SRQ2d 

½

”  – two-way 1/2 valve 

with actuator   

IP/Insulation class: IP20 
Power supply: 
200 – 240V 50/60Hz 
Max water temperature: +93

o

Max water pressure 
: 2,1MPa 
Kvs: 3,0 m

3

/h 

Opening time: 18 s 

 

 

SRQ3d 

½

”   – three-way 1/2 

valve with actuator

  

IP/Insulation class: IP20 
Power supply: 
200 – 240V 50/60Hz 
Max water temperature: 
+93

o

Max water pressure 
: 2,1MPa 
Kvs: 3,4 m

3

/h 

Opening time: 18 s 

 

 
 
 

Summary of Contents for ELIS Series

Page 1: ...TECHNICAL DOCUMENTATION OPERATION MANUAL DTR ELIS B 3 0 2016 02 02 EN ...

Page 2: ...he device without influencing its operation This manual is an integral part of the device and it must be delivered to the user together with the device In order to ensure correct operation of the equipment get thoroughly acquainted with this manual and keep it for the future The devices may only be installed and operated in conditions for which they have been designed Any other application inconsi...

Page 3: ...ectrical heat exchanger max range 5 m 2 TECHNICAL DATA B W 100 B N 100 B E 100 B W 150 B N 150 B E 150 B W 200 B N 200 B E 200 Power supply V Hz 230 50 3x400 50 230 50 3x400 50 230 50 3x400 50 Power consumption kW 0 34 0 42 7 5 0 36 0 44 11 5 0 38 0 49 15 5 Current consumption A 1 5 1 9 11 1 6 2 16 6 1 7 2 2 22 4 IP Insulation class 21 F Connecting stub Max water temperature o C 95 95 95 Max water...

Page 4: ...3 62 dB A 64 dB A 63 dB A 65 dB A 64 dB A 66 dB A 2 58 dB A 60 dB A 59 dB A 60 dB A 61 dB A 63 dB A 1 54 dB A 56 dB A 55 dB A 56 dB A 56 dB A 58 dB A Acoustic pressure level measured in the room of average sound absorption capacity 500m 3 at the distance of 3 m apart of the unit 2 4 AIR VOLUME step B W 100 B E 100 B N 100 B W 150 B E 150 B N 150 B W 200 B E 200 B N 200 3 2600 m 3 h 3500 m 3 h 4000...

Page 5: ... 2 330 353 360 0 7 0 8 0 9 15 0 14 5 14 0 2 8 2 9 2 9 83 85 86 0 1 0 1 0 1 9 0 8 5 8 5 10 6 6 7 1 7 2 290 310 316 0 6 0 6 0 7 19 0 18 5 18 0 2 5 2 5 2 6 72 74 75 0 1 0 1 0 1 13 5 13 0 12 5 15 5 7 6 1 6 2 248 266 271 0 5 0 5 0 6 22 5 22 0 21 5 2 1 2 2 2 2 62 63 64 0 1 0 1 0 1 18 0 17 5 17 5 20 4 7 5 0 5 1 204 220 225 0 3 0 4 0 4 26 0 25 5 25 0 1 8 1 8 1 8 51 53 53 0 1 0 1 0 1 22 5 22 0 22 0 Tw1 Tw2...

Page 6: ...W 200 PT Qw Δpw Tp2 PT Qw Δpw Tp2 Tp1 V kW l h kPa C kW l h kPa C C m 3 h Tw1 Tw2 90 70 o C Tw1 Tw2 80 60 o C 0 4000 4300 5200 27 6 28 7 31 8 1217 1266 1402 11 4 12 2 14 7 20 5 19 5 18 0 23 6 24 6 27 7 1038 1080 1195 8 7 9 4 11 3 17 5 17 0 15 5 5 25 8 26 9 29 7 1140 1186 1312 10 0 10 8 13 0 24 0 23 5 22 0 21 9 22 7 25 2 961 999 1106 7 6 8 2 9 8 21 1 20 5 19 5 10 24 0 25 0 27 7 1063 1105 1223 8 9 9...

Page 7: ...7 4 INSTALLATION 1 B A B 100 572 mm 1024 mm B 150 572 mm 1510 mm B 200 572 mm 2000 mm 2 Rozstaw szpilek C D E F B 100 133 770 mm 121 mm 561 mm B 150 182 1207 mm 122 mm 561 mm B 200 256 1621 mm 123 mm 561 mm 3 4 5 6 7 8 ...

Page 8: ...www flowair com 8 9 10 11 12 13 14 ...

Page 9: ...C DCm mechanical door contact Operating temperature range 10 80 o C IP Insulation class IP 65 Connectors 1xNC i 1xNO Max current resistive 10A inductive 3A Max Power load 300Vac or 250Vdc DCe magnetic door contact Operating temperature range 5 60 o C IP Insulation class IP 64 Connectors NC Max current inductive resistive 0 5A Max power Load 175Vdc Lenght of cabel 2m Max operating contactors distan...

Page 10: ...www flowair com 10 5 2 CONNECTING GUIDE 1 2 3 4 5 6 7 ELiS B W N 8 ELiS B E ...

Page 11: ... Address adjustment 2 MASTER mode operating SLAVE mode operating 3 Service 4 ELiS W N ELiS E 5 K1 Programme K2 Programme 6 Operating with thermostat Operating w o thermostat K1 programme Signal from door switch or thermostat is main signal for the device to run K2 programme Signal from door switch is main signal for the device to run and thermostat is in charge of valve heaters 5 3 1 REGULATION TS...

Page 12: ...ts opened door opened contacts closed ATTENTION Switch 4 on SW3 to the position E and then restart the system switching it off for 5 seconds Each time the device is switched off the heaters are being cooled for next 15 seconds 5 3 3 REGULATION T BOX ELIS B W N WIRING DIAGRAMS Power supply 230V 50Hz OMY 3x1mm 2 T box LIYCY 4x0 5mm 2 A and B braided wire pair max 50 m Door contact DCe DCm door close...

Page 13: ...ion E and then restart the system switching it off for 5 seconds Each time the device is switched off the heaters are being cooled for next 15 seconds 5 3 5 CONTROL SYSTEM MASTER SLAVE COMMUNICATION Electrical air curtain chaining provides control from 1 to 5 devices using one T box or TS Electrical air curtain chaining might be done by cable OMY 3x0 5mm 2 using connectors EL B EL A GND Connecting...

Page 14: ...l layer RS485 Protocol MODBUS RTU Baud rate 38400 bps Parity Even Data bits 8 STOP bits 1 Connection must be made using 3 poliges wire to connectors IN A IN B GND SIGNAL GROUND 5 3 7 CONTROL SYSTEM SETTING BMS ADDRESS DEVICE ADDRESS There is a possibility to set 31 addresses which are set binary on SW1 switch switch down switch up Addresses DRV 1 2 3 31 1 2 3 4 5 6 1 2 4 8 16 Y1 ...

Page 15: ... Air curtain thermostat on 5 0x08 ContactDoor 0 1 Door contact value set 0 DOOR_CLOSE Door closed 1 DOOR_OPEN Door opened Inputs Register Data Read Lp Modbus register address Name of parameter Min Max Description 1 0x04 CurtainFanSpeed 0 3 Air curtain fan speed value 0 FAN_SPEED0 Fan off 1 FAN_SPEED1 First fan speed 2 FAN_SPEED2 Second fan speed 3 FAN_SPEED3 Third fan speed 2 0x05 CurtainValveStat...

Page 16: ...9 OPERATION The device is designed for operation inside buildings at temperatures above 0 o C In low temperatures below 0ºC there is a danger of freezing of the medium The manufacturer bears no responsibility for damage of the heat exchanger resulting from freezing of the medium in the exchanger It is forbidden to place any objects on the heater or to hang any objects on the connecting stubs The d...

Page 17: ...rer bears no responsibility for operating the device in a manner inconsistent with its purpose by persons not authorized for this and for damage resulting from this Made in Poland Made in EU Manufacturer FLOWAIR GŁOGOWSKI I BRZEZIŃSKI SP J ul Chwaszczyńska 133A 81 571 Gdynia phone 48 58 669 82 20 fax 48 58 627 57 21 e mail info flowair pl www flowair com ...

Page 18: ...owing European Directives dyrektywy directives MD 2006 42 WE dyrektywy directives EMC 2004 108 WE oraz zharmonizowanymi z tymi dyrektywami normami and harmonized norms with above directives PN EN 60204 1 2010 Bezpieczeństwo maszyn Wyposażenie elektryczne maszyn Część 1 Wymagania ogólne Safety of machinery Electrical equipment of machines Part 1 General requirements PN EN 60335 1 2012 Elektryczny s...

Page 19: ...ść elektromagnetyczna EMC Część 6 1 Normy ogólne Odporność w środowiskach mieszkalnym handlowym i lekko uprzemysłowionym Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments PN EN 61000 6 2 2008 Kompatybilność elektromagnetyczna EMC Część 6 2 Normy ogólne Odporność w środowiskach przemysłowych Electromagnetic compatibili...

Page 20: ...www flowair com 20 ...

Reviews: