www.flowair.com |11
5.3. DRV ELIS CONTROL SYSTEM
Power supply 230V/50Hz;
Connectors for thermostat and fan step switch;
Door contact connector;
Valve actuator connector ELIS-..-W;
heaters contactor
connector ELiS-..-E;
BMS system connection;
T-box connectors;
MASTER-SLAVE connectors;
PT-1000 connectors;
LED INDICATORS:
G1, G2, G3 – signalize number of fan speed operating
S1, S2, S3 – signalize number of set fan speed
T – signalize of valve set
DC – signalize of door contact set
OPEN, CLOSE – signalize valve actuator
WORK – signalize of software working
SW3 – operating mode switch (default settings)
1
Device function
selection
BMS Address adjustment
2
MASTER mode
operating
SLAVE mode operating
3
Service
4
ELiS-..-W/N
ELiS-..-E
5
K1 Programme*
K2 Programme**
6
Operating with
thermostat
Operating w/o thermostat
*K1 programme – Signal from door switch or thermostat is main
signal for the device to run
**K2 programme – Signal from door switch is main signal for the
device to run and thermostat is in charge of valve/heaters
5.3.1. REGULATION TS – ELIS B-W/N WIRING DIAGRAMS
Power supply 230V/50Hz (OMY 3x1mm
2
)
Air curtain step switch with thermostat TS (OMY 5x0,5mm
2
)
•
Heat - heating mode
•
Fan - room thermostat deactivated
•
Cool - cooling mode
Door contact DCe/DCm (door closed – contacts opened; door opened – contacts closed)
Valve with actuator SRSQ3d (OMY 3x0,5mm
2
) or SRQ (OMY 3x0,5mm
2
)
A – Exchanger water supply
AB – Valve water supply
B – Return pipe water supply