USER MANUAL - WebdynEasy LoRaWAN
Version 0.10
/scheduler/schedules/schedule/start/dayofmonth
Trigger day in the month for the
first schedule iteration for a
“monthly” type schedule
Integer (min 1 max 31)
/scheduler/schedules/schedule/interval
Interval between occurrences (in
seconds)
Integer (min 0 max
4,294,967,295)
/scheduler/schedules/schedule/count
Number of occurrences
Integer (min 1 max
65535)
/modbus/tcp/timeout
Max. time without response from
Modbus/TCP slaves (in ms)
Integer (min 0 max
65535)
2000
/modbus/rtu/timeout
Max. time without response from
Modbus RTU slaves (in ms)
Integer (min 0 max
65535)
2000
/modbus/rtu/turnaround
Modbus RTU turnaround time (in
ms)
Integer (min 0 max
65535)
100
/modbus/datasets/dataset/
List of Modbus datasets
Integer (min 1 max
65535)
/modbus/datasets/dataset/id
Dataset identifier
Integer (min 1 max
65535)
/modbus/datasets/dataset/label
Dataset name
Text
/modbus/datasets/dataset/vars/var/
List of Dataset variables
/modbus/datasets/dataset/vars/var/name
Variable name
Text
/modbus/datasets/dataset/vars/var/type
Variable type
List:
•
S0: Coil (0X1/0X5,0XF)
•
S1: Discrete input (0X)
•
S3: Holding register
(0x3/0x6,0x10)
•
S4: Input register
(0x4)
/modbus/datasets/dataset/vars/var/address
1
st
variable register address
Hexadecimal 2 bytes
/modbus/datasets/dataset/vars/var/size
Variable size
Unsigned integer
/modbus/datasets/dataset/vars/var/format
Variable format
List:
•
raw
•
boolean
•
integer
•
float
•
ascii
/modbus/datasets/dataset/vars/var/flags
Variable options (optional)
List:
•
cmd_only
•
little_endian
•
no_opt
•
signed
•
is_status
•
is_alarm
/modbus/datasets/dataset/vars/var/threshold/low
Low threshold (optional)
Number (double)
/modbus/datasets/dataset/vars/var/threshold/high
High threshold (optional)
Number (double)
/modbus/datasets/dataset/vars/var/threshold/hysteresis
Hysteresis (optional)
Number (double)
/modbus/datasets/dataset/boundaries
●
/modbus/datasets/dataset/polling
Enable continuous polling
Boolean (true, false)
false
/modbus/modules/module/
List of Modbus modules
/modbus/modules/module/label
Modbus slave name
Text
/modbus/modules/module/dataset
Identifier of the dataset to use
Integer (min 1 max
65535)
/modbus/modules/module/address
Modbus slave Modbus address
Integer (min 1 max 247)
/modbus/modules/module/ip
Modbus/TCP slave IP address
IP format:
"xxx.xxx.xxx.xxx"
Or
Domain name:
"xxxxxxxxxx.xxx"
/modbus/modules/module/schedule
Modbus slave collection schedule
identifier
Integer (min 1 max
65535)
/system/log/level
Log trace level. Only for debug
(Contact support)
Level 1 (high) to 5 (low)
5
/system/password/admin
Administrator password
Text
high