USER MANUAL - WebdynEasy LoRaWAN 

Version 0.10 

Pin Mode 

Off

: The SIM card PIN code must be disabled 

Manual

: The SIM card PIN code must be entered in the 

PIN Code

 box 

PIN Code 

The SIM card PIN code must be entered if 

Manual

 is selected in 

PIN Mode

 

APN 

Your mobile operator’s APN name (required for an IP connection) 

Login 

Your mobile operator’s user name (optional depending on the operator) 

Password 

Your mobile operator’s password (optional depending on the operator) 

Mode 

OnDemand

: The hub only connects when it needs to communicate with the 

remote  server.  It  cuts  the  connection  when  the  data  transfer  is  complete 
after a duration that can be configured in 

Disconnect delay

AlwaysOn

:  The  modem  is  always  connected.  The  hub  uses  the  modem 

continuously for all IP communications.

 

AlwaysOff

: This mode should be used if there is an Ethernet connection to 

the remote server, but with a SIM card inserted in the hub.  The connection 
never uses the modem, but the hub can receive and send text messages.  

Disconnect 
delay (s) 

Waiting time value in seconds for 

OnDemand

 mode between the end of data 

exchanges and disconnection. 

 

 

Refer to your mobile operator to obtain the information for your SIM card 
(APN, login, password). 

 

5.1.1.2

 

Ethernet 

 

 

Parameters

 

Description 

IP 

The  IP  address  used  to  access  the  WebdynEasy  LoRaWAN  hub  via  the 
Ethernet network. 

Summary of Contents for Webdyn WebdynEasy LoRaWAN

Page 1: ...WebdynEasy LoRaWAN LoRaWAN gateway with external or embedded server USER MANUAL...

Page 2: ...pecifications 15 3 2 2 4 Software specifications 15 4 Installation and Maintenance 16 4 1 Unpacking 16 4 1 1 Product contents 16 4 1 2 Hub identification 16 4 2 Assembly 17 4 2 1 Opening closing the b...

Page 3: ...e upload File upload 46 6 Operation 47 6 1 The remote server 47 6 1 1 The FTP server 47 6 1 1 1 Configuration 47 6 1 1 2 Operation 48 6 1 1 3 File Format 49 6 2 The configuration 49 6 3 The data 51 6...

Page 4: ...specific and is used for end to end application data encryption It is required in ABP mode and is calculated automatically by the server during the JOIN in OTAA mode Data Rate The Data Rate is define...

Page 5: ...actor is the length of the sent frames The more the signal is spread the lower the speed However it increases the product range TCP Transmission Control Protocol An Internet based connection oriented...

Page 6: ...ersion V1 0 onwards 2 2 Target group This guide is intended for WebdynEasy LoRaWAN hub installers and users but also for people using our Sens RF LoRaWAN sensors 2 3 Product and accessory references L...

Page 7: ...n All wiring work must be carried out by a specialised qualified electrician Please follow all the safety instructions featured in the equipment documentation The WebdynEasy product can be damaged by...

Page 8: ...cording to the EU Declaration of Conformity available from Webdyn or on website www webdyn com Recycling The European directives enacted into national law covering battery waste and electric and elect...

Page 9: ...IP or RTU mode Principle diagram for a complete LoRaWAN solution 3 1 The LoRaWAN protocol LoRaWAN is a communication protocol that uses LoRa modulation This communication protocol uses several radio b...

Page 10: ...he hub is to collect LoRaWAN and or Modbus data and regularly send it to a remote server IS using Ethernet or 3G 4G 3 2 1 General description 3 2 1 1 Exterior Box front face 3 2 1 2 Interior Interior...

Page 11: ...ANUAL WebdynEasy LoRaWAN Version 0 10 SIM card holder Reset button RJ45 connector and LEDs BLE Bluetooth future use Request button identified FUNCTION on the board 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 11 12...

Page 12: ...CPU LED 7 LoRa Box output for external power supply Terminal block for external 12 24V power supply Box output for the 3G 4G modem external antenna option 3G 4G Modem SMA Antenna Mini USB connector r...

Page 13: ...m and 51 dBm 5 signal power 51 dBm Buttons Button Description Request Short press less than 2 seconds Connection request Long press more than 2 seconds Displays the Modem signal reception level see Mo...

Page 14: ...of European technical harmonisation legislation It is mandatory for all products covered by one or more European regulatory texts directives or regulations Symbol indicating that the waste must be co...

Page 15: ...Parameters Values Channels 8 simultaneous channels 863 870 MHz Europe 865 867 MHz India Max sensitivity 141dBm 125kHz in SF12 Supported DataRate DR0 DR5 Supported Bandwidth 125 250 kHz Max TX power 1...

Page 16: ...f there are missing or damaged items contact Webdyn support see section8 Support WebdynEasy LoRaWAN hub Ref WG0610 A01 The following are shipped with the hub a curved SMA antenna for the modem interna...

Page 17: ...conditions described in section 3 2 2 1 General specifications before installing as well as the following conditions Protect the product from dust moisture aggressive substances and corrosion The dis...

Page 18: ...can be wall mounted Before wall mounting first close the box see section 4 2 1 Opening closing the box Screws and anchors are not included in the kit You must choose the correct type of screw for the...

Page 19: ...se the 3G or 4G modem connection to allow the hub to communicate with the remote server the box must be opened see section4 2 1 Opening closing the box and a mini SIM card inserted into the SIM card h...

Page 20: ...preferable to configure it before the SIM card is installed see section 5 1 1 Hub connectivity There are three possibilities The PIN code is disabled modem communication is active The PIN code is enab...

Page 21: ...y attenuate radio waves End users must make sure their installation using remote antennas meets applicable EMC standards 4 2 5 Connection 4 2 5 1 Power supply The WebdynEasy hub must have a 12V or 24V...

Page 22: ...per data bus operation an RS485 bus must feature a 120 Ohm terminator at each end The WebdynEasy hub can be located at the end of the RS485 communication bus or in the middle As the hub has a 120 Ohms...

Page 23: ...or shielding must be connected to the hub box earth and not to the 0 V only connect one end of the screen Avoid any return trips in the same cable RS485 wiring on the hub side 1 Strip the RS485 commu...

Page 24: ...168 1 12 Subnet mask 255 255 255 0 DHCP Deactivated The next step is used to configure a PC network address to access the WebdynEasy LoRaWAN hub Configuring a second IP address on the PC 1 Under Windo...

Page 25: ...the subnet mask 255 255 255 0 7 Click Add 8 To validate the settings click OK in each one of the three windows 9 Close the Network connection and remote access window It is now possible to easily mod...

Page 26: ...are not supported IE 7 for example 2 Enter the hub IP address in your browser the default address is http 192 168 1 12 to access the WebdynEasy LoRaWAN home page 3 An identification window should be...

Page 27: ...N operation If web pages are accessed during the hub initialisation phase the logo is displayed Wait for the hub to be fully initialised to access the web pages 5 1 1 Hub connectivity The Connectivity...

Page 28: ...e connection when the data transfer is complete after a duration that can be configured in Disconnect delay AlwaysOn The modem is always connected The hub uses the modem continuously for all IP commun...

Page 29: ...for example www webdyn com into their corresponding IP addresses Enter the DNS server addresses you received from your internet service provider ISP here You can also enter your router IP address You...

Page 30: ...the hub clock synchronisation At the first connection NTP synchronisation is carried out and the next NTP synchronisation will be carried out during another connection after a minimum period of time T...

Page 31: ...pletely separate The Packet Forwarder can be used with a remote server and the embedded LoRaWAN server can use an external Packet Forwarder 5 1 2 1 Packet Forwarder In Packet Forwarder mode the Webdyn...

Page 32: ...ed at every FTP connection To use the hub Packet Forwarder enter the following IP address in Server address 127 0 0 1 Also check that the server ports Upstream server port and Downstream server port a...

Page 33: ...DR commands to the LoRaWAN sensor LoRaWAN sensor The server supports 2 activation modes ABP Activation By Personalization the DevAddr NwkSKey and AppSKey parameters must be entered OTAA Over The Air A...

Page 34: ...the remote FTP server see section 6 3 The data 5 1 3 System When the Modbus protocol is enabled on the RS485 port the serial port parameters must be defined Parameters Description Mode Off RS485 disa...

Page 35: ...transferred at the next connection Delayed The hub malfunction alarms Default are sent to the remote server immediately by default They can however be disabled Ignored or delayed Delayed and sent at t...

Page 36: ...nfigured as follows Parameters Description Id Unique schedule identifier The identifier must be an integer between 1 and 2 147 483 647 included Label Purely descriptive schedule name Type Daily Weekly...

Page 37: ...The Count value is between 1 and 2 147 483 647 included The Interval value is between 0 and 2 147 483 647 included Count If the schedule is to be triggered throughout the day at regular intervals you...

Page 38: ...aximum value namely 2 147 483 647 in Count Example Need Type Time Day of Week Day of Month Date Time Interval s Count Every Tuesday at 15 00 00 Weekly 15 00 00 Tuesday 0 1 Every hour between 8 00 and...

Page 39: ...mely 2 147 483 647 in Count Example Need Type Time Day of Week Day of Month Date Time Interval s Count Every 2nd day of the month at 00 00 00 Monthly 00 00 00 2 0 1 Yearly type schedule Every year the...

Page 40: ...n 8 00 and 20 00 on 31 December Yearly 2019 12 31T08 00 00 7200 7 Follower type schedule A Follower type schedule will be triggered after the end of every reference schedule occurrence The Parent sche...

Page 41: ...eout ms Modbus RTU response waiting time in ms Turnaround ms RTU turnaround time in ms TCP Timeout ms Modbus TCP response waiting time in ms a Modbus slave is defined by a label a dataset a Modbus add...

Page 42: ...eing defined by the following parameters Parameters Description Name Variable name for information only Type Variable type Coil 0x1 0x5 0xF Discrete input 0x2 Holding register 0x3 0x6 0x10 Input regis...

Page 43: ...e Write single Write multiple S0 Coil 0x01 0x05 0x0F S1 Discrete input 0x02 S3 Input register 0x04 S4 Holding register 0x05 0x06 0x10 The available formats are the following Format Description Coil Re...

Page 44: ...if the status changes the variable value is saved in the data file Below is a diagram describing the status changes depending on the thresholds and hysteresis If the variable is a status variable and...

Page 45: ...articular NTP synchronisation the INBOX directory check and indicates all the uploaded files 5 1 7 2 Reboot request Reboot This button is used to reboot the hub 5 1 7 3 Log download Download logs This...

Page 46: ...he following YEAR MM DDThh mm ss Where YEAR 4 digit year MM 2 digit month in the year DD 2 digit day in the month hh 2 digit hour mm 2 digit minutes ss 2 digit seconds The new date is only applied aft...

Page 47: ...r trigger actions on it The configuration or command files must be uploaded to the server in an INBOX directory associated with the hub Monitor the hub and assist in diagnosis The hub can upload hub s...

Page 48: ...pdate files Where uid Hub identifier timestamp The timestamp format is YEARMMDD HHMMSS so that an alphabetical sort of the directory gives the chronological order The data alarm and supervision files...

Page 49: ...the server are in XML format 6 2 The configuration The hub allows remote configurations using a configuration file or text messages Configuration file The WebdynEasy LoRaWAN hub configuration file is...

Page 50: ...r firmware version before sending it to your hub There is no need to send the entire configuration back to your hub A configuration file can be complete or partial A configuration file containing only...

Page 51: ...e server can be defined by a Schedule see section 5 1 5 Schedules and section 5 1 1 5 Upload However when connecting to the server following a manual request or the triggering of an alarm the hub take...

Page 52: ...In the same way as the configuration files All the files in this directory will be downloaded before being deleted and run The command file format is described by the command XSD file XSD files may c...

Page 53: ...retrieval Supervision text message log Log recovery Supervision modbus write Write on a modbus slave Alarm If several commands are sent at the same time the reboot factory and update commands can resu...

Page 54: ...after this command is sent No subcommands or parameters are required for this command Example By text message 6 5 5 Status command The status command is used to retrieve product status information Wh...

Page 55: ...written in the data attribute the list of slaves and registers in which the value must be written must be indicated The command is saved in the supervision actions and sent to the remote server SUPER...

Page 56: ...2 168 0 17 223 S3 0x0F52 Example By XML file By text message commands xmlns http www webdyn com GWL_command_20190719 xmlns xsi http www w3 org 2001 XMLSchema instance xsi schemaLocation http www webdy...

Page 57: ...IN directory on the remote server and an update command must be sent to the hub The update command can be sent either in a command file or by text message The command must include the name of the file...

Page 58: ...aint Germain en Laye Phone 33 1 39 04 29 40 email support webdyn com https www webdyn com Please have the following elements to hand Product type Product serial number Product hardware and software ve...

Page 59: ...client Boolean false true false com ethernet ip IP address IP format xxx xxx xxx xxx 192 168 1 12 com ethernet netmask Subnet mask IP format xxx xxx xxx xxx 255 255 255 0 com ethernet gateway Local n...

Page 60: ...xxx com time timezone Timezone in tz format List see http en wikipedia org wiki Zone tab com time alarm_threshold Alarm trigger threshold in seconds Integer min 0 max 65535 0 com time min_sync_interva...

Page 61: ...list separated by a comma alarm sources defaults delayed List of faults that cannot be sent immediately but only at the next connection D_MODEM D_MODEM_SIM_MISS D_MODEM_SIM_CODE_FAIL D_MODEM_PUK D_MOD...

Page 62: ...dataset vars var address 1st variable register address Hexadecimal 2 bytes modbus datasets dataset vars var size Variable size Unsigned integer modbus datasets dataset vars var format Variable format...

Page 63: ...867700000 lorawan channels channel Channel 8 frequency in Hz Whole number min 863 000 000 max 870 000 0000 867900000 lorawan packet_forwarder server address LoRaWAN server address embedded server 127...

Page 64: ...backup_interval Automatic configuration backup interval with the Fcntup and Fcntdown counters in seconds Whole number min 1 max 4 294 967 295 86400 lorawan server modules module List of LoRaWAN module...

Reviews: