USER MANUAL - WebdynEasy LoRaWAN
Version 0.10
little_endian
Interprets registers in little-endian
no_opt
A Modbus request will be used to read this variable
signed
The variable contains a signed value
is_status
Indicates that the variable contains an information status
is_alarm
All changes to the status variable will trigger an alarm
When the “is_status” option is defined, or at least one threshold is defined, the variable is
considered to be a status variable. This means that if the status changes, the variable value is
saved in the data file. Below is a diagram describing the status changes depending on the
thresholds and hysteresis.
If the variable is a status variable and the “is_alarm” option is present, an alarm file is
generated each time the status changes. The “is_alarm” option has no effect if the variable is
not a status variable (“is_status” option).
When the monitoring parameters
Threshold low, Threshold high
or
Threshold
hysteresis
are used, the
Polling
mode must be enabled to monitor the variable
continuously.
5.1.7
Run actions
The web interface “Actions” tab is used to run certain actions locally.
5.1.7.1
Remote server connection request. Request