Commissioning
instr
DYNAVERT
®
L05
34
Stand/ issue: 25.07.03
4BS0516DE-EN/011
4.4 Commissioning
fault
The most occuring commissioning faults are:
No.
Setting faults
Consequences
1.
Switch-off points for the braking distances are
shorter than the respective parameterised braking
distances
Jerky approach and stopping
2.
Parameterised braking distance
P-TRAVEL CURVE DATA : BrkDis v... is shorter than
displayed in menu I.MIN.BRAKE.DIST. : BrkDis v...
There appears the fault message:
“Alloc. V ... >< brk.dst. ...“
3.
Accel. or Decel. too high or not equal (see item 4.3.1)
Current limit was reached too fast
4.
Motor type plate data misread
Motor noises, vibrations, motor does
not start
5.
Speed sensor or motor (phase sequence) wrong
connected
Fault message “Diff set/act” or motor
“jerking”
6.
Motor speed controller not optimized
Motor noise, vibrations, untrue running
of motor