7.7 Top-up, operation with the water treatment module
11-5
Wartung
Treatment
quantity reset
Perform action
Maintenance
Fig. FM.056.V01.15
8-2-1
Treatment
activate
edit mode?
Perform action
Top-up
Reset the treated quantity:
Required after each change of the
treatment module. Observe error
message nos.: 55; 61; 31; page 28.
When reset, the value in field 4 of the
operating menu [10] changes from
the previously processed quantity to:
00000 l
Caution:
Resetting to: 00000 l without replacing
the module, and without verifying
the residual capacity, leads to an
unacceptable quality of the top-up
water!
Changing the treatment volume
Required if the default value (300 litres)
does not match the capacity of the initial
module, or the preset value of the used
module does not match the capacity
of the module changed. (Impulse water
counter standard: 10 l / Imp.)
Caution:
The use of an incorrect value can lead to
unacceptable quality of the top-up water
or prevent the use remaining capacities!
7.8 Malfunction messages
Procedures and values for error identification, evaluation and output have been tried in practice, prevent secondary failures and
invite user awareness. Please note that incorrect set-up conditions can lead to repeated errors and inhibit the intended use.
Examples of incorrect set-up conditions are: incorrect or no longer applicable design, outdated equipment, incorrect installation
and inadmissible operational parameters.
Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value
Error message
number
-
Voltage spike sensor (short circuit)
ON
1
-
Pressure sensor > 20 mA
ON
2
Signal out of sensor range or short circuit, no pressure read-
out; lockshield valves in return connection in incorrect position
/ check electrical installation, threaded round connector, sensor
range (4-20 mA; 16 bar), return connection, change sensor if
necessary
» service; Error off: self-resetting when error resolved.
-
Pressure sensor < 4 mA
ON
3
Signal below sensor range or not connected, no pressure read-
out / check electrical installation, threaded round connector,
sensor range (4 -20 mA; 16 bar), change sensor if necessary »
service; Error off: self-resetting when error resolved.
-
Volume sensor > 20 mA
ON
4
Signal out of sensor range or short circuit, no volume readout /
check electrical installation, threaded round connector, sensor
range (FSI 1: 150-300; 2: 400-800; 3: 1000-2000; 4: 2500-5000;
5: 6500-10000), change sensor if necessary» service; Error OFF:
self-resetting when error resolved.
-
Volume sensor < 4 mA
ON
5
Signal out of sensor range or not connected, no volume read-
out/ check electrical installation, threaded round connector or
sensor range; change sensor if necessary» service; Error OFF:
self-resetting when error resolved.
Fig. FM.055.V01.15