Heat recovery unit RDAF - Technical manual
7
FläktGroup DC_9349GB_20190326_R4
We reserve the right to make changes without prior notice
SELECTING OPERATING STATUS
The symbol on the home screen shows the operating status. Press the
centre of the fan symbol to change the status.
Normal mode (manual)
Heating stove mode, makes it easier to light a heating stove
or open fireplace. Temporarily creates overpressure in the
house.
ALARMS
The symbol on the home screen shows the alarm status.
No alarm
Alarm B
Alarm A
Press the icon to enter the alarm screen.
TEMPERATURES
Here you set the desired supply air temperature (setpoint).
Note: This value is not to be confused with the desired in-
door temperature, which is managed by the domestic heat-
ing system. The recommended setpoint is 16–19 °C. The
factory setting is 18 °C. Temperatures, output signals etc.
are read-only values.
FAN STATUS
Supply and extract air fan speeds can be read from
30 –100 % or as 0 (off).
AIR QUALITY
Air quality (only available if optional moisture control or CO
2
control is activated). Relative humidity of the supply and ex-
tract air can be read from 0-100% RH.
The setpoint and current CO
2
value (up to 2,000 ppm) can
be read.
SYSTEM OVERVIEW
Version control panel -- -- -- -- -- -- -- -- -- -- -- --IP Octet 1
Bootloader control panel - -- -- -- -- -- -- -- -- -- - IP Octet 2
Version control card - -- -- -- -- -- -- -- -- -- -- -- - IP Octet 3
Bootloader control card -- -- -- -- -- -- -- -- -- -- --IP Octet 4
Unit type
TIME SCHEDULES
(Not applicable to domestic ventilation).
SETTINGS
See pages 17–18..
CLEARING ALARMS
To clear an individual alarm, press Acknowledge after the relevant
alarm. To clear all the alarms, press Acknowledge All button (top right).
If the alarm cannot be cleared, it will reappear on the display and the
underlying cause for this must be resolved before the alarm can be
cleared.
A built-in timer is normally set to provide a filter replacement reminder
(alarm) every six months. If a shorter replacement interval is required
(before the alarm is due) the filter alarm can be reset under the Set-
tings menu. See page 22, fig. 3.
MENU
Example 1 No alarm
Example 2. Active alarms
ALARM HISTORY
ISYTEQ TOUCH 3.5 CONTROL PANEL - OPERATION