Heat recovery unit RDAF - Technical manual
23
FläktGroup DC_9349GB_20190326_R4
We reserve the right to make changes without prior notice
PARAMETER LIST
Note that incorrect parameter settings can cause moisture problems, operational disruption and other types of malfunction.
For this reason, the settings must be configured by suitably qualified professionals.
1)
L/S = Editable value, L = Read-only value
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
Supply air temperature
L
-40-100
°C
–
Outdoor air temperature
L
-40-100
°C
–
Extract air temperature
L
-40-100
°C
–
Setpoint
L/S
15-35
°C
18
Desired supply air temperature
Summer / Winter mode
L
Summer / Winter
–
–
Output signal Postheater
L
0-100
%
–
Option
Output signal Preheater
L
0-100
%
–
Option
Output signal Rotor
L
0-100
%
–
Output signal Cooling
L
0-100
%
–
Not applicable to domestic ventilation
Control mode / Current setpoint
L
15-35
°C
–
TEMPERATURES
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
Supply air fan speed
L
0 or 30–100
%
–
Extract air fan speed
L
0 or 30–100
%
–
FANS
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
Relative humidity Supply air
L
0-100
% RH
–
Relative humidity Extract air
L
0-100
% RH
–
Moisture active
L
Yes / No
–
–
Moisture control active or inactive
CO
2
level
L
0-2000
ppm
–
Current CO
2
level in extract air
Setpoint CO
2
L
0-2000
ppm
800
AIR QUALITY
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
Software version control panel
L
–
–
–
Bootloader version control panel
L
–
–
–
Software version control card
L
–
–
–
Bootloader version control card
L
–
–
–
Unit type
L
–
–
Domestic
IP Octet 1
L
0-255
–
–
Current IP address, accessory
IP Octet 2
L
0-255
–
–
IP Octet 3
L
0-255
–
–
IP Octet 4
L
0-255
–
–
SYSTEM OVERVIEW
Parameter
Type of value
1)
Range
Unit
Standard value
Comment
Time schedules
L
–
–
–
Activated time channels, read-only
TIME SCHEDULES