Heat recovery unit RDAF - Technical manual
22
FläktGroup DC_9349GB_20190326_R4
We reserve the right to make changes without prior notice
CO
2
CONTROL
CO
2
control is only active at normal speed. At low and high speed, set
the fan speed in % of max. speed.
1. Set the desired CO
2
setpoint.
2. Choose the minimum limit.
This specifies whether the minimum limit should be low or normal
speed. The speed cannot go below this value.
3. Set the relationship between the extract air and the supply air. The
extract air is the master and the supply air is the slave.
To complete the adjustment, click the check mark.
CONTROL PANEL OPERATION, COMMISSIONING