Installation instruction
FläktGroup
DC_8658GB 20181214_R0
We reserve the right to make changes without prior notice
14
GENERAL INSTRUCTIONS
UNITS STACKED ON TOP OF ONE ANOTHER
(ONLY FOR EQGA, EQGB)
Units of the same width can be stacked on top of one another.
Up to two size 005-032 units can be stacked on top of one
another.
EQGA, EQGB
Double deck
Unit sizes 005-032
If the units are of different widths, arrange the inspection sides
so that they are in the same plane. Place an angle profile under
the rear frame profile of the top unit (length = length of lower
unit) and fit a bar for height compensation under the front frame
sectiion.
Fit EQAZ-16-01-1 sealing strip around the opening of the empty
section before fitting the upper unit.
The EQAZ-16-30-1 (sizes 005-090), EQAZ-16-50-1 (unite sizes
108-216) jointing piece set is used for securing the upper units to
the lower as shown.
The set consists of 6 angle brackets. Use the angle bracket as
a template and secure it to the frame section with self-tapping
screws. (Spacing, max. 1.5 m.)
Important!
The EQAZ-16-30-1 or EQAZ-16-50-1 angle
brackets must always be secured to the air
handling unit in the version for outdoor
installation.
EUGA 13
for example
Empty section
(inlet, bottom)
for example.
Fan section
(outlet upward)
Flat bar
Angle iron