3 | Commissioning
FISCHER Mess- und Regltechnik GmbH
14 / 32
BA_EN_MS13
3.3 Menu levels
The menu levels are structured as follows:
End
menu level
Menu Level
Switch points
Menu Level
Input
Menu Level
Measuring
Menu Level
Output
Menu Level
Function
Menu Level
Display
Menu Level
System
End
menu level
Reception
Output
Output
Illustration 15:
Menu levels
The following tables provide an overview of the parameters of the individual
menu levels. In the Menu Level Systemyou can change to the respective na-
tional language using the language parameter. You can see which languages
are supported there.
3.3.1 Menu Level Switch points
Parameter name
Description
Value range
SP1 On
Switch point 1 On
MBA-50% … MBE+50%
SP1 Off
Switching point 1 off
MBA-50% … MBE+50%
SP1 delay
Switching point 1 delay
0…1800 s
SP1 Function
Switching point 1 function
NO, NC
SP2 On
Switch point 2 On
MBA-50% … MBE+50%
SP2 Off
Switching point 2 off
MBA-50% … MBE+50%
SP2 delay
Switching point 2 delay
0…1800 s
SP2 Function
Switching point 2 function
NO, NC
The two switching outputs are configured by four parameters respectively.
For the switch point 1 these are