3 | Commissioning
FISCHER Mess- und Regltechnik GmbH
22 / 32
BA_EN_MS13
Parameter name
Description
Value range
Auto1: Red-green
Auto2: Red-yellow-
green
Lighting
Lighting time
0 s, 10 … 600 s
Contrast
Contrast
15 … 45
Bar chart
Barchart display
yes, no
Basic measuring range
MA
ME
F1
F2
F3
F4
Illustration 20:
Function Auto2
MA
MB-start
Measuring range start
F1
Red-Yell.switch.
Colour-change red to yellow
F2
Yell.-Gr.switch.
Colour-change yellow to green
F3
Gr.-Yell. switch
Colour-change green to yellow
F4
Yell.-Red switch
Colour-change yellow to red
ME
MB-end
Measuring range end
In this menu the same parameters are used as those described in the previous
sections.
NOTICE
Unused range
If a range is not to be used, the associated switch thresholds (F1…F4) can be
set to the same value.
Example
The parameter Colour is set to Auto2. Only the green, yellow and red ranges
are required here. To fade out the lower ranges red and yellow, the switch
thresholds "red-yellow switching" and "yellow-green switching" are set to the
start of the measuring range.
Basic measuring range
MA
ME
F1
F2
F3
F4
Illustration 21:
Example Auto2
3.3.7 Menu Level System
Parameter name
Description
Value range
Language
Language change
DE, EN, FR, ES,
IT,PT,HU