![Fischer Panda AGT 4000 PVMV-N Handbook Download Page 76](http://html1.mh-extra.com/html/fischer-panda/agt-4000-pvmv-n/agt-4000-pvmv-n_handbook_2294280076.webp)
Installation Instructions
Page 70 Panda AGT-DC 4000 PVMV-N s00670 - Chapter E: Installation Instructions
29.12.04
10.Terminal clamp for external automatic start - allocation:
15: Battery minus (-)
16: Input for external start demand
The potential-free contact can be connected to these two terminal. The starting sequence occurs
automatically if the contact closes.
11.Fuse 1,6A slow to blow
12.Switch for the starter motor cut-off voltage:
Switch 1: 12V - generator
Switch 2: 24V - generator
Switch 3: 36V - generator
Switch 4: 48V - generator
Attention! Only one switch may remain switched „ON“, all others must be switched „OFF“,
otherwise the complete generator could break down! An external voltage-cut-off-switch is
neccessary for voltages exceeding 48 Volts.
13.Compensation potentiometer for (12)
Is set at the factory.
14.Soldering bridge for choice of pre-glow time
• Soldering bridge open - pre-glow time 8 sec.
• Soldering bridge closed - pre-glow time 4 sec.
Attention! The panel-circuit board voltage is dangerous if the battery voltage exceeds 60
Volts. The panel must be mounted, that the voltage carrying points can not touched. This
is also the case during testing.
1.
Operating and starting the Generator will works with the Control Panel. This implementing the
Main Switch (7) is effected for. By switching 'On' the Main Switch the Generator will be at first in
operaton modus. After pressing the button 'Start' (7) the Generator (Motor) will be aglow and star-
ting. Pay attention, the button (7) will only be hold down for a second to ignitiate the start proce-
dure.
2.
Therefore with the panel it is possible, monitoring the operation modus. Hereto are beeing pla-
ced four diodes ( LED), which are connected as a pair each other, so they have the possibility to
light up in green or red.
These are:
(3) for exhaust, cooling water temperature
(4) Control unit meter - oil pressure
(5) Control unit meter - operating status
(6) Control unit meter - charge control
If (2), (3) or (4) is been illuminated red, this lights will indicate the precise cause. Illuminate con-
stant green the genset is in operation modus.
In the starting sequence, (2) is been illuminte green, (3,4,5) red,is there no fault all diodes beco-
mes green or green flashing when the generator runs.
Summary of Contents for AGT 4000 PVMV-N
Page 64: ...Generator Failure Page 58 Panda AGT DC 4000 PVMV N s00670 Chapter D Generator Failure 29 12 04...
Page 90: ...Appendix Page VIII Panda AGT DC 4000 PVMV N s00670 Chapter F Appendix 29 12 04...
Page 94: ...Measurements Page XII Panda AGT DC 4000 PVMV N s00670 Chapter F Appendix 29 12 04...