General operation
10.5.11
Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation Seite/Page 145
With (+) characterized connection is the input.
The input is connected through a resistance to 12V (with 24V-operated internally generated). If the two connections
are short circuited over a potential-free contact, then the input current flows.
To be considered for an electronic contact the low input current and the polarity is to be selected.
The high input current is to be selected for an electromechanical contact.
The input is debounced (delay time approx.1s).
On the input an external voltages must not be set.
Fig. 11.7.2-1: Data
Fig. 11.7.2-2: Settings
Attention:
The automatic adapter must only be used together with a
device. The starter should only be switched on when the gene-
rator stationary (shut-down)!
Data:
Parameter
Information
Operation voltage
The automatic adapter power is supplied via the generator control panel P6+. The
same absolute maximum ratings obtain as with the generator control panel P6+.
Operation temperature
The same absolute maximum ratings obtain as with the generator control panel
P6+.
Proper power consumption
10mA - 20mA
Tolerance of times
± 10%
8-pole DIP-switch S1 settings (S1.1 to S1.8):
standard
S1.1
S1.2
S1.3
S1.4
S1.5
S1.6
S1.7
S1.8
Heat-time
2,5s
OFF
OFF
5s
ON
OFF
10s
X
OFF
ON
20s
ON
ON
Start-time
8s
X
OFF
16s
ON
Stop-time
16s
OFF
OFF
32s
X
ON
OFF
64s
OFF
ON
128s
ON
ON
Operation-mode
Normal
X
OFF
Test (all times over 16)
ON
Input current
1,25mA
OFF
7mA
X
ON