Generator Failure
4.5.16
Kapitel/Chapter 8: Generator Failure - Seite/Page 103
insulated casing, which prevents heat loss.
Fig. 8.6.2-1: Failure bypass switch
Failure bypass switch
This period can be reduced by pushing the button on the front of the generator. The generator can be started by
means of the remote control as long as the button is depressed. The switch/button bypasses any faults allowing the
generator to run.
Before depressing the button, a manual check of the oil dip stick must be carried out to determine whether the gene-
rator has sufficient oil, as it is possible that the oil pressure switch causes the generator to cut out. If it has been
ascertained that the reason for the motor cutting out is overheating and not lack of oil, the generator can be run for
several minutes without load, so that the motor is cooled by the circulating coolant.
BEWARE:
If the temperature is the reason for the generator cutting out when it is running under load, then an immediate check
must be made to determine the cause. It could be a fault with the cooling system, one of the fans, the air-intake or a
fault with the external cooling system.
Continual use of the starter-failure bypass switch should be avoided, while the generator cuts out during operation.
The generator must always run without load for several minutes before being switched off, so that a temperature
compensation occurs. Heat accumulation can cause the generator to overheat, even after it has been switched off.
Should the overheating alarm be set off, caused by heat accumulation, after the generator has been switched off,
then this can also be bypassed using the switch.
8.6.3 Stop solenoid
There are two different variations:
A. Energized to stop
By pressing the „OFF“-button on the remote control panel the stop solenoid is supplied with voltage and operate,
through this the injection nozzles resets to zero position and the generator stops.
B. Energized to run
This version is equipped with two solenoids an actuating and a stop solenoid. After being fed with current, the actua-
ting solenoid attracts the adjusting lever of the fuel injection pump, through which the fuel can flow. The actuating
solenoid is switched off once the final position has been reached, which is maintained by the stop solenoid for as
long as the generator is running
Summary of Contents for 15000i PMS
Page 10: ...Seite Page 10 Kapitel Chapter 2 4 5 16 Leere Seite Intentionally blank...
Page 70: ...Installation Instructions Seite Page 70 Kaptitel Chapter 5 Installation Instructions 4 5 16...
Page 112: ...Tables Seite Page 112 Kaptitel Chapter 9 Tables 4 5 16...
Page 176: ...Seite Page 176 Kapitel Chapter 16 Annex 4 5 16 Leere Seite Intentionally blank Annex...