DTC 100/4 TD
Trouble-shooting guide
TROUBLE
POSSIBLE FAILURE
REMEDY
Thermostat inoperative
Plug not connected
Connect plug in socket
Water cools down during
night
-Selector switch not in AUTO
position
-One of retaining valves
of the system inoperative
(enables thermosiohon water
circulation)
-Set the switch to AUTO
position-Check machine
installation. We recommend
installation of motor actuated
ball valve “EMV110 800/230..”
When pumps are active,
unpleasant noise in
installation is heard
Retaining valve makes noise
(weak spring)
Replace nonreturn valve with
motor actuated ball valve
“EMV110 800/230..”
Irrespective of the
temperatures, all pumps
are inoperative
Selector switch in position
“OFF”
Temperature limit of hot water
tank too low
Set selector switch to AUTO
position Increase max.
temperature in hot water tank
(see: Temperature regulation
in hot water tank)
Irrespective of the temp.,
collector pump is
continuosly switched on
and after-heating pump is
inoperative
Selector switch in “ON1”
position
Set the switch to AUTO
position
Irrespective of the temp.,
after-heating pump is
continously switched on
and collector pump is
inoperative
Selector switch in “ON2”
position
Set selector switch to AUTO
position
Collector pump operates
normally and after heating
pump not
After-heating circuit discon-
nected
Connect after-heating circuit
See: Settings
After-heating pump
operates normally and
collector pump not
Collector circuit disconnected
Connect collector circuit
See: Settings
Control light of individual
pump is on, but the pump
is inoperative
Pump blocked or cable of the
pump interrupted
Check the pump and
connection to regulator
When “T1” key is pressed
Er1 appears
T1 sensor is interrupted
Check T1 sensor
When “T1” key is pressed
Er2 appears
T1 sensor is short circuited
Check T1 sensor
When “T2” key is pressed
Er1 appears
T2 sensor is interrupted
Check T2 sensor
When “T2” key is pressed
Er2 appears
T2 sensor is short circuited
Check T2 sensor
When “T3” key is pressed
Er1 appears
T3 sensor is interrupted
Check T3 sensor
When “T3” key is pressed
Er2 appears
T3 sensor is short circuited
Check T3 sensor
Er1 is shown on display
T4 sensor is interrupted
Check T4 sensor
Er2 is shown on display
T4 sensor is short circuited
Check T4 sensor
Summary of Contents for EMV 110 502 Series
Page 2: ...page 2...
Page 4: ...page 4...
Page 5: ...page 5...
Page 10: ...page 10...
Page 11: ...page 11...
Page 12: ...page 12...
Page 13: ...page 13...
Page 14: ...page 14...
Page 15: ...page 15...
Page 16: ...page 16...
Page 17: ...page 17...
Page 26: ...page 26 EXAMPLES OF USE...
Page 28: ...page 28...
Page 29: ...page 29...
Page 44: ...page 44...
Page 54: ...page 54 DTC 100 2 TDG HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 57: ...page 57...
Page 58: ...page 58...
Page 72: ...page 72 DTC 100 4 TD HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 75: ...page 75...
Page 76: ...page 76...
Page 89: ...page 89...
Page 90: ...page 90...
Page 103: ...page 103...
Page 104: ...page 104...