101
DTC 200
3.3 ELECTRIC CONNECTION
1(1)A, 250V
DTC 200 (4 sensors)
3. Heating the domestic hot water from two heating sources
(solar collectors, boilers, heat pump...) in one water tank - DTC
200 (4 sensors).
In this case of use is DTC200 in function of double differential
thermostat. It is used for heating the domestic hot water in one
water tanks from two heating sources (collector-boiler or collec-
tors east-west). Differential thermostat controls motorised ball
valves and pump for each heating circuit.
3.1 Basics
The thermostat enables setting two parameters:
1. Regulation of maximum temperature in hot water tanks from
10° to 90°C.
This temperature is defined by T2 and T4 sensors witch are
generally mounted in upper third of heat exchangers.
2. Regulation of temperature difference between primary heating
source (T1) and exchanger (T2) from 0K to 15K.
3. Regulation of temperature difference between secondary heat-
ing source (T3) and exchanger (T4) from 0K to 15K.
With these regulations you define how much the value of the
source temperature (collector, boiler...) should exceed the tem-
perature of water around the exchanger in hot water tank, that
the thermostat opens the valve and activates the pump.
The difference is set in relation to the volume of heat losses of
the system that depend on lengths of pipelines from source to
hot water tank and on pipeline insulation.
3.2 Operation
DTC 200 is double differential thermostat measures the tem-
perature of two heating sources (collectors, boilers,…) and of
two spots in user (hot water tank). Heating effect is provided,
when heating unit(heating element in hot water tank) exceeds
the temperature of the user for set difference.
When the temperature of the source exceeds the temperature
around the exchanger for set difference, the thermostat opens
the valve (EMV110..) and activates the pump.
Thermostat closes the valve and switch of pump, when tem-
perature difference is lower than pre-set value. Thermostat also
switches off a pump if pre-set temperature is reached in hot
water tank.
When pump operates for primary heating circuit (collectors),
operation of after-heating circuit is prevented. This assures
maximum energy savings during seasons and this also the main
role of solar systems.
For those applications you need four sensors. Two of them are
mounted into individual heating sources and two into upper
half of individual exchangers in hot water tank. T1 and T2 are
designed for primary (main) heating circuit which heats entire
quantity of water in hot water tank (lower exchanger), where T1
is a sensor of heating source (generally collectors) and T2 is a
sensor in lower part of hot water tank. T3 and T4 are designed
for additional, i.e. after-heating circuit which additionally heats
water in hot water tank (upper exchanger). T3 is a sensor of
heating source (generally boiler) and T4 is a sensor in upper
part of hot water tank.
Grounding wires should be
connected to special ter-
minal pins situated on left
side of terminal strips.
The thermostat is
designed for fixed
installation. When
performing electric instal-
lation, an element should
be inserted which enables
at least 3 mm separation of
thermostat from the mains
(switch or socket). Prior
to each intervention in the
thermostat, first disconnect
it from the mains.
Before each intervention in the thermostat first discon-
nect the main power!
TERMINAL
CONNECTION
1,2
sensor T1 - primary heating source (collector, solid fuel
boiler…)
2,3
sensor T2 - hot water tank
4,5
sensor T3 - secondary heating source (boiler…)
4,6
sensor T4 - secondary hot water tank
11
N - neutral
12
L - phase - pump for primary circuit
1(1)A, 250V
, 50Hz
13
N - neutral
14
L - phase -pump for secondary circuit
1(1)A, 250V
, 50Hz
15
L - phase mains 230V
, 50Hz
16
N - neutral mains 230V
, 50Hz
1(1)A, 250V
Summary of Contents for EMV 110 502 Series
Page 2: ...page 2...
Page 4: ...page 4...
Page 5: ...page 5...
Page 10: ...page 10...
Page 11: ...page 11...
Page 12: ...page 12...
Page 13: ...page 13...
Page 14: ...page 14...
Page 15: ...page 15...
Page 16: ...page 16...
Page 17: ...page 17...
Page 26: ...page 26 EXAMPLES OF USE...
Page 28: ...page 28...
Page 29: ...page 29...
Page 44: ...page 44...
Page 54: ...page 54 DTC 100 2 TDG HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 57: ...page 57...
Page 58: ...page 58...
Page 72: ...page 72 DTC 100 4 TD HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 75: ...page 75...
Page 76: ...page 76...
Page 89: ...page 89...
Page 90: ...page 90...
Page 103: ...page 103...
Page 104: ...page 104...