page
39
Standard adapters for
mounting on mixing
valves:
By special orders we supply adapters for folowing mixing
valves:
FIRŠT Rotomix F3 in
F4, ACASO,
Landis&Gyr, Besser,
IKA, V.I.L.B., Meibes,
Termomix, Besser,
MUT, FIRŠT Rotomix
MSVA, MSVBA,
Ferrotherm, ESBE,
IMP, IMT, Honeywell
LŽ, Sauter, Centra
(ZRK), API, Danfoss,
Tekmar, TEM, Barberi
Viessmann, Centra, V.I.L.B., TVT-STADLER ,
Honeywell (medeninasti ), Vailant, VITA, Meibes, AEG, IKA,
Caleffi, MUT 1000, ...
ACTUATOR WITH MIXING VALVE
ACTUATOR WITH VENTILATION FLAP
We reserve the right to changes in manual and of technical characteristics of the product without previous notice.
FIRŠT-ROTOTEHNIKA, s.p.
, Radegunda 54, SI-3330 Mozirje,
tel: +386 3 898 35 00, fax:+386 3 898 35 35, e-mail:[email protected], http://www.first.si
SLOVENIJA
T E H N I C A L D A T A
ye/gr
blue
brown
black
grey
E L E C T R I C C O N N E C T I O N
e x e c u t e a c c o r d i n g a b o v e s h o w n w i r i n g d i a g r a m . T o c h a n g e t h e r o t a t i n g d i r e c t i o n
i n t e r c h a n g e t e r m i n a l s 1 a n d 3 . B e s i d e t h i s d o n o t f o r g e t t o r e p o s i t i o n a l s o c u r v e f o r p u m p f o r a p p r o p r i a t e o p e r a t i n g .
P o w e r s u p p l y . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R o t a t i o n a n g l e . . . . . . . . . . . . . . . . . . . . . . . . . .
R o t a t i o n t i m e f o r 9 0 . . . . . . . . . . . . . . . .
O u t p u t t o r q u e . . . . . . . . . . . . . . . . . . . . . . . . . . .
P r o t e c t i o n d e g r e e . . . . . . . . . . . . . . . . . . . . .
E l e c t r i c m o t o r i n s u l a t i o n c l a s s . .
A m b i e n t t e m p e r a t u r e . . . . . . . . . . . . . . . . .
M i c r o s w i t c h r a t i n g . . . . . . . . . . . . . . . . . . . . .
C o n n e c t i o n c a b l e l e n g t h . . . . . . . . . . . .
W e i g h t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
°
2 3 0 V , 5 0 H z , 3 . 5 W
p r e s e t t o 9 0 , p o s s i b l e f r o m
1 5 u p t o 3 4 0
2 1 0 s
6 N m
I P 5 5
E 1 2 0
0 . . . 5 5 C
5 ( 1 ) A , 2 5 0 V A C
5 x 0 . 7 5 m m , L = 1 5 0 0 m m
0 . 9 5 k g
°
°
°
°
°
1
L
N
2
M
4
3
5
N
PRESSETING THE CURVES
WARNING: BEFORE EVERY OPENING DISCONNECT THE ACTUATOR FROM LINE VOLTAGE !
Curves are factory pre set to enable rotation of actuator for 90°. In case of different desired rotation angle you can set the rotation angle from
15°up to 340°.
Turn the actuator into base position by electricity. Open the
cover of actuator and manual preset the curves :
- With curve signed on draving below with 1, starting position of
mixing valve.
- With curve number 2 preset end position of mixing valve
- The curve signed on drawing with 3, act third micro switch,
which i most of application turn on and off the pump.
It is advisable to preset third curve to deactivate micro switch
before curve for start position deactivate micro switch for
basic position.
After setting the curves fit the cover.
Those position are valid by factory electrical wiring.
When you electrically change the rotation, while signal for
open is feed to terminal 1 and for close on terminal 3, the
meaning of curves are opposite. Take care in this case for
appropriate setting of curve 3 for pump switch!
Presetting of curves should be done by a qualified person !
NOTE: Rotating direction of curves is opposite from rotating direction of actuators output axis.
NOTE:
T O P V I E W
micro switch for pump
c u r v e 1
c u r v e 2
c u r v e 3
S I D E V I E W
micro switch for
start ( 1 ) position
micro switch for
end ( 2 ) position
Summary of Contents for EMV 110 502 Series
Page 2: ...page 2...
Page 4: ...page 4...
Page 5: ...page 5...
Page 10: ...page 10...
Page 11: ...page 11...
Page 12: ...page 12...
Page 13: ...page 13...
Page 14: ...page 14...
Page 15: ...page 15...
Page 16: ...page 16...
Page 17: ...page 17...
Page 26: ...page 26 EXAMPLES OF USE...
Page 28: ...page 28...
Page 29: ...page 29...
Page 44: ...page 44...
Page 54: ...page 54 DTC 100 2 TDG HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 57: ...page 57...
Page 58: ...page 58...
Page 72: ...page 72 DTC 100 4 TD HOLES FOR EASIER INSTALLATION OF DIFFERENTIAL THERMOSTAT ON WALL...
Page 75: ...page 75...
Page 76: ...page 76...
Page 89: ...page 89...
Page 90: ...page 90...
Page 103: ...page 103...
Page 104: ...page 104...