ROTOTERM MR-TR

1

www.first.si

ROTOTERM MR-TR “plus”

 is weather 

compensating central heating controller. It is 

designed to regulate the radiator or underfloor 

heating. The controller is 3-point (PID) temperature 

controller of heating water, which works as a 

function of external temperature, and in conjunction 

with the room correction unit, allows remote room 

temperature adjustment.  

The controller is built in microprocessor technology 

and meets the latest quality standards. It offers 

a wide variety of programming options, allowing 

optimal controller settings for the selected object. 

Features:

LED’s indicate control output status

• 

Output for controlling motor actuator for mixing 

• 

valves (UNI 3P, MV120) and circulation pump

Pump and valve exercise (every 72h for 30s) 

• 

which helps prevent sticking during long periods of 

inactivity

Service switch to assist installer on start-up and 

• 

technician during service

Sensors fault status on digital display

• 

Factory set default parameters

• 

Digital setting of all parameters

• 

Temperature enquiry (outer, boiler, underfloor, 

• 

mixed flow) on digital display

 

Code

Description

21128

ROTOTERM MR-TR plus

(Heating controller MR-TR, Room unit AS 2000-E, sensors AF, BSVF, BF, 

mounting kit) 

21131

ROTOTERM MR-TR 

(Heating controller MR-TR, sensors AF, BSVF, BF, mounting kit) 

DATA SHEET

Micro-processor heating controller 

for controlling radiator or under floor heating

ROTOTERM MR-TR

Characteristics:

Supply voltage: 230VAC, 50Hz

• 

Power consumption: max.4VA

• 

Power supply of users: 1(1)A, 230VAC, 50Hz

• 

Room temperature setting range: 5 - 25°C

• 

Heat curve ratio adjustment: 0,1 - 2°C

• 

Heat curve parallel shift adjustment: +/- 10°C 

• 

Room unit influence (AS/VF):  1 - 15

• 

Max. mixed flow temperature setting range: 

 

• 

30-85°C

Boiler condensation limit adjustment: 30-75°C 

• 

(radiator heating)

Underfloor temperature limit adjustment: 15-35°C 

• 

(underfloor heating)

Circulation pump switching-off adjustment:  

• 

20-45°C

Sensors type: KTY 81-210 

• 

Programmable Room unit AS 2000-E

Room unit AS 2000-E is designed for daily and 

• 

weekly mode of operation and for setting two 

temperature levels (day - night).

The possibility of correction room temperature or 

• 

mixed flow temperature (function is chosen on the 

right side of the unit )

Control of actual hour, day and heating status 

• 

Room temperature display

• 

Kit weight:   ROTOTERM MR-TR plus 1,1kg 

• 

     

ROTOTERM MR-TR 0,9kg

ROTOTERM MR-TR plus

ROTOTERM MR-TR

Summary of Contents for 21128

Page 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Page 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Page 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Page 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Page 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Page 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Page 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Page 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Page 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Page 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Page 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Page 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Page 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Page 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Page 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Page 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Page 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Page 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...