First 21128 Manual Download Page 10

ROTOTERM MR-TR

10

www.first.si

2nd example 

Room temperature in transition period corresponds but is too high in cold periods.

In this case the slope of heating curve [n] should be set to lower value.

transition 

period

cold 

period 

4. TEMPERATURE LIMIT OF MIXED FLOW: [o]

          from: 

to

Temperature limit of mixed flow is used in systems where smaller areas of under floor are heated with pipes of radiator heating 

(bathrooms, toilet rooms). To prevent damages of under floor systems or under floor linings (ceramic tiles) the temperature in pipes 

should be limited under certain temperature value (50°C). Such limit value, used in radiator heating systems, prevents fast rise of 

temperature of heating units during very cold mornings; consequently the time required to reach the desired room temperature is 

extended.  Therefore in this case it is recommended to pre-set the time for morning start up of heating

WARNING:

 If the temperature of heating water line for radiator heating is limited to too low value it is possible that very low morning 

temperatures prevent reaching of required room temperature.

Considering the type of heating the controller enables the following settings:

Under floor heating: 

from 30°C to 50°C (factory setting 50).

Radiator heating:

 from 30°C to 85°C (factory setting 80).

5.PUMP SWITCHING OFF: [c]

 

               from: 

to

This setting specifies the temperature at which the controller switches off the pump, when mixing valve is already closed. This 

function enables that all heating units are uniformly cooled down after termination of higher operating mode.

Factory settings of deactivation: radiator heating: 30°C, under floor heating: 25°C.

6. INFLUENCE OF ROOM UNIT: [E]

 

               from: 

to

This setting specifies the degree of increase or decrease of the temperature of heating water line if room temperature changes for 

1°C. Higher is the inertia of the system, lower should be the influence of room unit and vice versa.

Under floor heating:

 the influence of room temperature can be set between 0 and 5 (factory setting 3); 

radiator heating:

 between 

0 and 15 (factory setting 8).

When MR-TR controller is used solely as temperature controller of mixed flow with reference to out side temperature (without room 

unit), the terminal pins 5 and 6 remain free.

IN THIS CASE THE INFLUENCE OF ROOM UNIT MUST BE SET TO 0!

3rd example 

Room temperature in transition period too low but in cold period corresponds.

4th example 

Room temperature in transition period too high but in cold period it corresponds.

1st step 

Increase parallel shift of curve [P] to higher value.

2nd step

Set ratio of heating curve [n] to lower value.

1st step 

Increase parallel shift of 

curve [P] to lower value.

2nd step

Set ratio of heating curve 

[n] to higher value.

transition 

period

cold 

period 

transition 

period

cold 

period 

transition 

period

cold 

period 

transition 

period

cold 

period 

Summary of Contents for 21128

Page 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Page 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Page 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Page 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Page 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Page 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Page 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Page 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Page 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Page 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Page 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Page 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Page 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Page 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Page 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Page 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Page 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Page 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...

Reviews: