MOUNTING OF SENSORS

MOUNTING OF OUTSIDE AIR SENSOR AF 2000

Fix the sensor to the north side wall (or shady side) of the building at least 1.5 m 

from the un der floor and from all possible heat sources (win dow, door, ventilating 

channels, stacks, direct sunlight, above the win dows…)

Connect the sensor cable to the terminal pins 1 and 2 in the au to matics connection 

box.

MOUNTING OF CLAMP-ON SENSOR VF 2000 - to the mixed flow line

Mount the sensor at least  20 cm above the mixing valve before or after the pump, as close-fit 

sensor on the mixed flow hose under the iso lation or as immersion sensor in the cap. 

Be careful not to let the sensor cable to touch the hot pipes (use proper isolation). Provide good 

contact with the heating water line and apply thermal isolation. Connect it to terminal pins 3 and 

4 in the controller connection box.

MOUNTING OF FLOOR SENSOR VF 2000 - for under floor heating only

Mount the sensor into flexible hose as close to the com po sition under floor surface as possible, 

somewhere in the middle of the feeding and returning conduit.

Do not place it under thick carpet or furniture. 

Be careful not to let the sensor cable to touch the hot pipes (use proper isolation) and apply 

thermal isolation. Connect it to ter mi nal pins 7 and 8 in the controller connection box. 

If you don’t install the sensor,

 the terminal pins 7 and 8 should be connected to 2 k

resistance and parameter [t] set to value 35 

(see setting of tem pera ture limits for under floor - parameter [t]). In that case you don’t have protection against floor overheating.

MOUNTING OF BOILER SENSOR KF 2000 - for radiator heating only

Mount the sensor into the cap next to the other boiler sensors. In case of 4-way mixing valve it 

can also be mounted as close-fit sensor to the heating water line after the furnace out put. 

If you don’t install the sensor

, the terminal pins 7 and 8 should be connected to 2,9k  and 

parameter [t] set to value 30 (see setting of temperature limits for under floor - pa ram eter [t]).  

 

In that case you don’t have protection against boiler condensation.

Use the enclosed bolts and mount the room unit to the wall. The unit shall be fixed at least 1.5 m above the floor and at least 1m 

away from all heating sources (radiator, sun influences, fire places, ...

).

ASSEMBLY OF ROOM UNIT AS 2000-E 

(ROTOTERM MR-TR “plus” only)

If the room unit AS 2000-E is used as remote temperature corrector (correction of heating curve) is installation is not important 

because the unit operates independently of the ambient temperature.

This  happens  in  cases  where  in  the 

existing  space  are  used  additional 

sources of heating - fireplace. In this case 

side switch for selecting operation (see 

description of the room unit AS2000-E) 

shifted to the OFF position (factory set 

to ON). This will enable heating of  other 

room in the building by heating curve.

WARNING!

In this position, a switch (5) in position 

“ ”  does  not  provide  protection 

against  frost  (room  temperature 

8-10°C), but the function of full-OFF 

operation - unconditionally closes the 

mixing valve.

When an additional heating source is no longer active, switch (14) moves back to ON, which provides us with a constant temperature 

in the room.

Some examples of incorrect installation

Heating 

source

Chimney

Gas

boiler

Summary of Contents for 21128

Page 1: ...display Code Description 21128 ROTOTERM MR TR plus Heating controller MR TR Room unit AS 2000 E sensors AF BSVF BF mounting kit 21131 ROTOTERM MR TR Heating controller MR TR sensors AF BSVF BF mounti...

Page 2: ...t When used with radiator version the sensor is located into the boiler in order to prevent condensation or overheating of the boiler In case the boiler temperature falls bellow the condensing tempera...

Page 3: ...5 The under floor sensor of the controller prevents the under floor to get too hot thus prevents the unpleasant feeling of warmth in your feet When used with radiator version the sensor is located in...

Page 4: ...pins PIN CONNECTION 1 2 Put side air sensor AF 2000 3 4 Mixed flow sensor VF2000 grey colour 5 6 Room unit AS2000 5 9 6 9 7 8 Floor sensor BF2000 or boiler sensor KF2000 red colour 9 N Neutral condui...

Page 5: ...ltage cables 2 If the distances between sensors and controller are larger over 15 meter it is recommended the installation of VDR resistance of 25V It is installed by soldering at the point where the...

Page 6: ...se you don t have protection against floor overheating MOUNTING OF BOILER SENSOR KF 2000 for radiator heating only Mount the sensor into the cap next to the other boiler sensors In case of 4 way mixin...

Page 7: ...ars Sensor cables shall not be placed parallel to live power supply cables as in case of electric shock there is danger of induced current which can damage the controller or room unit In case that pow...

Page 8: ...fference Troom between actual room temperature and required room temperature When T2 BF KF key is pressed the display shows floor temperature or temperature in the boiler When T3 AF key is pressed the...

Page 9: ...t can be modified by means of heating curve ascent or descent Range of parallel curve shift for heating curve 1 0 SELECTION OF HEATING CURVE Heating curves represent an interconnection between outside...

Page 10: ...to This setting specifies the temperature at which the controller switches off the pump when mixing valve is already closed This function enables that all heating units are uniformly cooled down afte...

Page 11: ...value of ratio Programming is executed in three procedures For easier understanding see the diagram on the following page First procedure set the ratio of heating curve and parallel shift Second proce...

Page 12: ...Additionally it is equipped with room temperature display Room unit AS 2000 E has additional switch on the right side It makes possible to choose two heating regimes temperature control of mixed flow...

Page 13: ...inutes 10 key for setting hours 11 key for setting the day of the week 12 key for input the program 13 key RESET deletes time and program 14 Slide switch for unit operation ON temperature control of m...

Page 14: ...of operation There are two operating modes if the switch 14 in the ON position provides frost protection room temperature 8 10 C if the switch 14 in the OFF position heating is switched off closes mix...

Page 15: ...o a lower temperature On the display appears symbol which indicates switching to higher temperature 2 First switching cycle for switching to higher temperature On display appears symbol for first sett...

Page 16: ...xt switch cycle etc Temporary heating regime change Temporary change of regime is valid till next switch cycle When you re in automatic mode slide switch 2 in position AUTO press to change the regime...

Page 17: ...to position AUTO program is not set See the example of program settings the program is incorrectly configured for each switch cycle to a higher temperature is followed switch cycle to a lower temperat...

Page 18: ...T3 sensors If T2 or T3 key is pressed Er2 is displayed Sensor T2 or T3 short circuited Check T2 and T3 sensors The controller operating normally Sometimes it happens that the controller repeatedly re...

Reviews: