background image

®

 

5

 

 

 

 

 

 

7.  INSTALLATION

 

During the installation, all components have to be protected from impact or bending. 

 

 

WARNING: DURING PILOT INSTALLATION THE RECOMMENDATIONS IN THE 
APPENDIX 2 SHOULD BE STRICTLY OBSERVED. 

 
SP-48-FD

 pilot’s air tube 

can be welded directly to the burner plate, or placed in the mounting tube (see Fig. 2). 

It should be noted that the distance from the gas head with mounting ring to the burner plate should be not less than 
150 mm and insertion depth cannot exceed the “L” value – see Fig. 1.

 

 

Pilot air tube is made of stainless steel, mounting tube is made of carbon steel which must be noted for welding. 

Note: Particulates entrained in the gas could block the pilot’s gas orifices so gas supply line should be equipped 
with an effective strainer unit. 

 

 

WARNING:    STRICTLY  OBSERVE  THE  TEMPERATURE  LIMITS  FOR  PILOT 
AND IGNITER ROD MOUNTED INSIDE. IN THE CASE OF EXPECTED WORK AT 
THE  LIMIT  OF  PERMISSIBLE  OPERATING  TEMPERATURES,  APPROPRIATE 
MEASURES SHOULD BE TAKEN (E.G. CHANGE OF THE MOUNTING POSITION). 
WHEN BOILER OR HEATER INSTALLATION IS IN OPERATION ALWAYS KEEP 
THE PROPER AIRFLOW OF PILOT COMBUSTION-COOLING AIR.

 

 

 

7.1  MOUNTING TUBE

 

The mounting tube, if used, should be attached to the burner plate using bolts or welding (see Fig. 2). If it is not 
possible to use one of mounting tubes proposed above, a different type can be used, bearing in mind that its inner 
diameter should be properly matched to the outer diameter of the pilot air tube to be able to fit and fix the pilot in 
a tube with proper clearance.

 

In the case of application including a mounting tube proceed the following way:

 

a) 

Based  on  assembly drawings  mark  and  cut  a  hole  in  the  burner  plate  with  a  diameter slightly larger than 
the diameter of the mounting tube.

 

b) 

The  mounting  tube  for  welding:  slide  the  mounting  tube  in  the  hole  and  set  it  in  the  correct  position 
(insertion depth and proper angle relative to the main burner nozzle position).

 

c) 

The mounting tube for welding: weld using the electrode appropriate for the material.

 

d) 

If the flanged mounting tube is used, bolt it to the burner plate after drilling the correct sized holes.

 

7.2  GAS ASSEMBLY AND AIR TUBE

 

a)   The position of the electric igniter rod tip in relation with the orifice-stabilizer assembly of pilot should be 

checked  following  information  in  p.  4.  The  correct  position  for  different  types  of  electrical  igniter  rods 
should be taken into consideration (see Fig. 1).  
It should be remembered that the rod tip positioning against the swirler-stabilizer plate in the pilot gas part 
assembly (pos. 1 on Fig.1) should be done outside the air tube only.  
Only  after  proper  rod  positioning  should  the  rod  be  fixed  by  tightening  the  gland  and  the  whole  gas 
assembly with rod inserted into the air tube. 

b) 

Mounting of electrical igniter rod in a pilot: unscrew the rod tip, disassemble the gland, put all gland 
parts  on  rod,  insert  the  rod  in  gas  head,  screw  back  the  rod  tip  and  then  set  the  appropriate  tip 
position relative to an orifice-stabilizer assy. Now the gland can be screwed onto gas head tightly

. In 

case  of  problems  sliding  the  rod 

through  rings  of  fixing 

gland  apply  a  small  amount  of  high  temperature 

resistant grease or grind slightly the gland ring inner surface. 
After setting the correct rod position, fasten the rod fixing gland in the gas head. Then the complete gas part 
assembly can be slid into the air tube.  
Do not remove the rod from fixing gland if it is not necessary, as the gland rings once clamped on rod do 
not allow easy rod movement. 

Summary of Contents for SureFire II SP-48-NG-FD

Page 1: ...d each unit is checked and tested before dispatch Acquaintance with the following instructions and strict attention to the indications reduce the possibility of equipment failure to a minimum and ensu...

Page 2: ...xits the main nozzle at the outlet of the air tube The main flame then stabilizes in the primary combustion zone at the outlet of the air tube The swirler stabilizer plate and holes in air tube provid...

Page 3: ...he Fireye High Tension Igniter the end of the rod tip should be placed at a distance of 10 mm back from the swirler stabilizer see Fig 1 In case of the High Energy Spark Igniter the rod tip should be...

Page 4: ...ling the pilot burner please follow the rules below 6 1 Use pilot only for its intended purpose 6 2 At the time of installation operation and maintenance follow the procedures described in the instruc...

Page 5: ...he burner plate with a diameter slightly larger than the diameter of the mounting tube b The mounting tube for welding slide the mounting tube in the hole and set it in the correct position insertion...

Page 6: ...tors may be used c To ensure a long and trouble free operation of the pilot it should be kept clean Check the condition of the gas pipe and if the orifices are not blocked Remove all buildups Hoses sh...

Page 7: ...flame stabilizes at the end of the air tube and reaches a blue yellow color If the airflow is too low the end of the air tube may start to glow it starts to glow at 400 500 C as the main flame burns i...

Page 8: ...the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of sequence timin...

Page 9: ...does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The preset gas...

Page 10: ...intenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts other than original 1...

Page 11: ...ght 3 0 m ins length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Parts Part No Description SP 48 MTF Mounting Tube...

Page 12: ...12 APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Page 13: ...us pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube tip can be mounted in the throat or in the swirler Pilot tip cannot extend beyond the he...

Page 14: ...nd especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas pilot d...

Page 15: ...5 cubic foot ft3 Air flow rate 1 cubic metre hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig x 4 01...

Page 16: ...is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND...

Reviews: