11.2 In case of air tube wear or damage:
–
if air tube or mounting ring has to be replaced - order a replacement air tube (with mounting ring) of length
“L” – prices on request only,
–
if just the end of air tube is eroded - cut 200 mm of the tube tip, order and weld spare part
P/N
SP-48-END
- replacement air tube end, length 200 mm, SS310/330.
List of pilot spare parts Part Numbers is in Table 2.
11.3
The warranty (see page 16) covers delivered devices and materials under conditions of proper
installation, start-up, operation and maintenance, it means the use in accordance with applicable
instructions and manuals.
This is particularly applicable to overheated parts i.e. working above their maximum operating
temperature defined in Instruction Manual.
11.4 The defective device or part will be replaced or repaired at manufacturer’s option.
The warranty applies to and may be executed only on a failed device send to the manufacturer warehouse for
examination or warranty repair.
11.5 The manufacturer does not accept liability for damage to persons or property resulting from:
–
mechanical damages,
–
improper installation, operation, maintenance of igniter contrary to the instructions in the user manual,
–
unauthorized igniter modifications or repairs made by unauthorized personnel,
–
use of components or spare parts other than original.
11.6 During the guarantee period any repairs must be carried out by the manufacturer service department, or the user,
upon the service's notification and consent.
11.7 Replacement of the consumables
can be user-performed only after expiration of the guarantee.
FIGURE 5.
Loose Spare Parts set for SP-32 and SP-48 pilots
Loose Spare Parts set includes:
1 - rod gland ½” NPT (for
SP-32
and
SP-48
) – 1 pc
2 - gasket OD 25x5 (for
SP-32
) – 1 pc
3 - O ring 46x3 (for
SP-48
) – 1 pc
4 - thumb screw M4 with snap ring
(for
SP-32-ND
and
SP-48-ND
) – 1 pc
12. STORAGE
SP-48
gas pilot should be stored in a clean, dry environment and in its original packaging if possible.
In case of long length pilots, always keep them in a horizontal position by supporting both ends and in the middle. It
should also be protected from contamination using caps on gas and air inlet and pilot outlet and covered with foil.
Storage over 30 days: relative humidity of no more than 85%, temperature below 50°C.
NOTICE
:
THE MANUFACTURER RESERVES THE RIGHT TO CARRY OUT
MODIFICATIONS TO THE PRODUCT DESCRIBED IN THIS INSTRUCTION MANUAL
AT ANY TIME AND WITHOUT ANY ADVANCE NOTICE.
.
1
2
3
4