74
£
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
20.5
Oxygen Input function
0- Monitor only
1- Closed loop trim
20.6
Oxygen probe calibrate enable
0- Not selected
1- Calibrate in air
2- Calibrate in reference gas
20.7
Boiler transport delay
5-60 seconds
20.8
Reset oxygen trim profile
0- No Reset
1- Reset learned trim profile
20.9
Automatic trim commissioning
0- Not selected
1- Automatic trim commissioning
23.0
Trim Limit default
0- Not selected (trim limit fixed at ± 5%)
1- Selected (trim limit adjustable ±25%)
23.1
Trim limits Profile 1
0.0-25.0
23.2
Trim limits Profile 2
0.0-25.0
23.3
Trim limits Profile 3
0.0-25.0
23.4
Trim limits Profile 4
0.0-25.0
24.1
Trim Integral Gain Profile 1
0.0-99.9%
24.2
Trim Integral Gain Profile 2
0.0-99.9%
24.3
Trim Integral Gain Profile 3
0.0-99.9%
24.4
Trim Integral Gain Profile 4
0.0-99.9%
25.0
Trim Proportional Gain default
0- Not selected.
1- Selected (Proportional Gain available for each profile)
25.1
Trim Proportional Gain Profile 1
0.0-99.9%
25.2
Trim Proportional Gain Profile 2
0.0-99.9%
25.3
Trim Proportional Gain Profile 3
0.0-99.9%
25.4
Trim Proportional Gain Profile 4
0.0-99.9%
26.0
Inlet Temperature Sensor
0- Not Fitted
1- For calculated burner GROSS efficiency.
2- For calculated burner NET efficiency.
26.1
Calorific Values of fuels/profiles 1
0.0-99.9%
26.2
Calorific Values of fuels/profiles 2
0.0-99.9%
26.3
Calorific Values of fuels/profiles 3
0.0-99.9%
26.4
Calorific Values of fuels/profiles 4
0.0-99.9%
26.5
Hydrocarbon ratios of fuel for Profile 1
0-9.99%
26.6
Hydrocarbon ratios of fuel for Profile 2
0-9.99%
26.7
Hydrocarbon ratios of fuel for Profile 3
0-9.99%
26.8
Hydrocarbon ratios of fuel for Profile 4
0-9.99%
26.9
Boiler Radiated Heat Loss
0-9.99%
COMMISSIONING SHEET