Option 9.6 - Setpoint 2 warming time (0 - 999)
If the boiler’s measured value remains below the warming limit set in option 09.5 for longer than the
warming time set here in minutes, the boiler will be allowed to modulate normally.
Options 10.0 to 10.9 - Auxiliary input functions
Option parameters 10.1 to 10.9 determine the functions of the 10 auxiliary inputs.
Please note, only auxiliary inputs A to E may be set and used for safety critical functions
[14 to 20]. Refer to Aux. A to E inputs in wiring section for terminal designations. If more than
one input is selected to have the same function, the “lower number” input is used. Refer to following
page for details.
Option Parameter
10.0
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
Input Channel
1 (PF1 - PF2)
A (PF11 - PF12)
B (PF13 - PF14)
C (PF15 - PF16)
D (PF17 - PF18)
E (PF19 - PF20))
2 (PF1 - PF3)
3 (PF1 - PF4)
4 (PF5 - PF6)
5 (PF5 - PF7)
Default Function
Fault mute
None (must be selected)
None (must be selected)
None (must be selected)
None (must be selected)
None (must be selected)
Gas select
Oil select
Air pressure switch 2 FLOW
Air pressure switch 2 NO FLOW